Checking After Commissioning - Huawei NetCol8000-A013 User Manual

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
2.
3.
4.
Step 8 After the commissioning is complete, remove the device used for charging the
refrigerant, and install the valve bonnet.
Step 9 Exit the diagnostic mode.
----End

4.7 Checking After Commissioning

Table 4-8 Check items
Check Item
No oil stain exists on the copper pipe
thermal insulation foam or bottom
plate.
The needle valve plug is secured
(torque of 0.45±0.05 N·m), and the
valve bonnet is tightened.
The foreign matter inside the water
pan and bottom plate is cleaned up.
The air filter is correctly installed.
Issue 04 (2022-11-25)
In diagnostic mode, start the wet film humidifier.
Check that the water inlet pipe does not leak during the process.
In diagnostic mode, close the wet film humidifier.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Power-On Commissioning
Result
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed