Huawei NetCol8000-A013 User Manual page 43

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
Figure 3-2 Oil trap (unit: mm)
Gas Pipe, Liquid Pipe, and Thermal Insulation Foam (Optional)
Table 3-4
Table 3-4 Specifications
Item
Liquid pipe
Gas pipe
Thermal insulation
foam
Water Pipe
Figure 3-3
Issue 04 (2022-11-25)
lists the specifications for pipes and thermal insulation foam.
shows how to connect a drainpipe.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Specifications
3/8 inch (9.52 mm), wall thickness: 0.75 mm; pressure
withstanding capacity ≥ 4.5 MPa
3/4 inch (19.05 mm), wall thickness: 1.0 mm; pressure
withstanding capacity ≥ 4.5 MPa
≥ 13 mm