Status Control Element (Icon) Is Operated Via A Separate Object - ABB IP Touch 7 Manual

Abb i-bus knx dca ets-app
Table of Contents

Advertisement

2.7.6

Status control element (icon) is operated via a separate object

Options:
An additional 1-bit communication object "Switch status" is enabled via the parameter.
Deactivated: The communication object is not available.
Activated: The status display of the control element indicates the current status of the
object. The feedback object can ensure that the correct status is always displayed.
If an actuator has a separate feedback object, this additional object can check whether the
actuator has switched. For this the feedback object of the actuator must be connected with
the feedback object of the button via a common group address (Action).
If the status display is not activated via a feedback object, the control element always
changes to the other status when actuated.
The following supplementary parameter is available for selection "Activated":
Type of feedback signal:
Options:
The parameter is used to specify what the feedback object sends back.
 
Product manual 2CKA001473B5023
Control elements and application parameter
Deactivated
Activated
1 bit
2x1 Bit
1 byte [0 - 100%]
1 byte [0 - 255]
"Blind" control element
│79

Hide quick links:

Advertisement

Table of Contents
loading