2.7.4

Type of control

Options:
The parameter is used to specify whether commands to move the blinds and adjust the slats
are sent to linked blind actuators via short or long actuations of the the buttons.
Short = stepwise/stop, long = move: A short press of the button triggers a command to
adjust the slats or a stop command. A long press of the button triggers a move command.
The following supplementary parameter is available:
Long operation after ...:
Options:
The parameter is used to set how long the button must be pressed to recognize a long
operation.
Short = move/stop, long = stepwise: A short press of the button triggers a move command.
A long press of the button triggers a command to adjust the slats or a stop command. The
following supplementary parameter is available:
Long operation after ...:
Options:
The parameter is used to set how long the button must be pressed to recognize a long
operation.
Repeat of all "Stepwise/stop" telegrams:
Options:
The parameter is used to set the space of time between two "Stepwise/stop" telegrams.
Short = move/stop: At each short actuation the following commands are sent consecutively
to linked blind actuators:
Move command
Stop command
Move command
Stop command
etc.
 
Product manual 2CKA001473B5023
Control elements and application parameter
Short = stepwise/stop, long = moving
Short = moving/stop, long = stepwise
Short = moving/stop
Setting option from 0.3 - 10 seconds
Setting option from 0.3 - 10 seconds
Setting option from 0.3 - 10 seconds
"Blind" control element
│77