ABB DRL6600U Product Manual

ABB DRL6600U Product Manual

Disturbance recording and fault locating device

Advertisement

Quick Links

Disturbance recording and
fault locating device DRL6600U
Product guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB DRL6600U

  • Page 1 — Disturbance recording and fault locating device DRL6600U Product guide...
  • Page 2: Table Of Contents

    4CAE000359 Disturbance Recording and Fault Locating Device DRL6600U Product version: V8.30 Issued: May 2017 Revision: - Contents Overview ................................2 Available functions ............................3 Recording mode ............................... 7 Current recording ............................. 8 Variation current recording ..........................8 Delta current recording ............................ 8 Residual overcurrent recording ........................
  • Page 3: Overview

    Revision: - 1. Overview DRL6600U Disturbance Recording and Fault Locating DRL6600U consist of a recording unit with CPU and Device for power system is adapted to substations, hard disk and a separate HMI. It uses the CPU and industrial use, railways, and power generation of each...
  • Page 4: Available Functions

    4CAE000359 Disturbance Recording and Fault Locating Device DRL6600U Product version: V8.30 Issued: May 2017 Revision: - 2. Available functions Table 1: Main functions Name Description ANSI IEC60617 IEC61850 I over Phase overcurrent recording I> I2 over Negative-sequence overcurrent recording I2>...
  • Page 5 4CAE000359 Disturbance Recording and Fault Locating Device DRL6600U Product version: V8.30 Issued: May 2017 Revision: - Name Description ANSI IEC60617 IEC61850 Over frequency Over frequency recording f> Low frequency Low frequency recording f< DF div dt Rate-of-change frequency recording Df/dt>...
  • Page 6 4CAE000359 Disturbance Recording and Fault Locating Device DRL6600U Product version: V8.30 Issued: May 2017 Revision: - Table 2: Controlling and monitoring function Name Description ANSI IEC60617 IEC61850 I over Phase overcurrent recording I> I2 over Negative-sequence overcurrent recording I2> 3I0 over Residual overcurrent recording IN>...
  • Page 7 4CAE000359 Disturbance Recording and Fault Locating Device DRL6600U Product version: V8.30 Issued: May 2017 Revision: - Name Description ANSI IEC60617 IEC61850 Disturbance A disturbance recording will be formed and recording saved when a trigger is registered. Manual recording Manual triggering generates a recording file...
  • Page 8: Recording Mode

    4CAE000359 Disturbance Recording and Fault Locating Device DRL6600U Product version: V8.30 Issued: May 2017 Revision: - 4. Recording mode Trigger 0-50 Cycles 150 Cycles 0-25 Cycles 1-10KHz 1-10KHz 0.5-10kHz Start time of T-0 Start time recording of disturbance Figure 1: A-B-C Recording and IO time sequence...
  • Page 9: Current Recording

    4CAE000359 Disturbance Recording and Fault Locating Device DRL6600U Product version: V8.30 Issued: May 2017 Revision: - 5. Current recording 6. Phase voltage recording Variation current recording Overvoltage recording When the power system is disturbed for some reason When supplying power over an underground cable or a...
  • Page 10: Rate-Of-Change Frequency Recording

    Based on the impedance at the time the short circuit happens, the DRL6600U automatically calculates and determines the distance between the device and the fault point.
  • Page 11: Operation

    12. Monitoring Time Synchronization Analog signal sampling monitoring Clock synchronization makes comparison of events DRL6600U acquires and stores data from current and and disturbance data among all IEDs in the system voltage channels with a sampling frequency of 10kHz. possible.
  • Page 12: Hmi (Human-Machine-Interface)

    4CAE000359 Disturbance Recording and Fault Locating Device DRL6600U Product version: V8.30 Issued: May 2017 Revision: - 14. HMI (Human-machine-interface) The LHMI consists of the IED front panel and an HMI. There are status and operation indicators on the IED front panel.
  • Page 13: Hardware Description

    4CAE000359 Disturbance Recording and Fault Locating Device DRL6600U Product version: V8.30 Issued: May 2017 Revision: - 16. Hardware description RESET RESET BCODE RESET AC IN- AC IN+ DC IN- DC IN+ POWER FAULT Figure 2: Device module Table 4: Module description...
  • Page 14: Connection Diagram

    4CAE000359 Disturbance Recording and Fault Locating Device DRL6600U Product version: V8.30 Issued: May 2017 Revision: - 17. Connection diagram A total of 96 analog inputs can be accommodated. AC current and AC voltage modules can be configured according to the actual project requirements. The highest permissible voltage for voltage channels is 180V, and largest current for current channels is 40I is 1A or 5A, please note clearly in the order form).
  • Page 15 4CAE000359 Disturbance Recording and Fault Locating Device DRL6600U Product version: V8.30 Issued: May 2017 Revision: - Figure 4: Binary input terminal diagram, up to 192 binary input connections are supported...
  • Page 16: Mounting Method

    4CAE000359 Disturbance Recording and Fault Locating Device DRL6600U Product version: V8.30 Issued: May 2017 Revision: - 18. Mounting method This device commonly adopts panel mode mounting. A=465mm B=450mm D=133.3mm C=532.2mm E=190.6mm G=Φ8-M5(Or M6) F=133.3mm Figure 5: IED mounting cut-out dimension diagram...
  • Page 17 4CAE000359 Disturbance Recording and Fault Locating Device DRL6600U Product version: V8.30 Issued: May 2017 Revision: - A=465mm B=450mm C=89.5mm D=76.2mm Φ9 mm (4-9x9) Figure 6: Keyboard and mouse carrier cut-out dimension diagram Figure 7: Display hanging bar cut-out dimension diagram A=482.6±0.2mm...
  • Page 18: Technical Data

    4CAE000359 Disturbance Recording and Fault Locating Device DRL6600U Product version: V8.30 Issued: May 2017 Revision: - 19. Technical data Table 5: 12U, 19" case IED device dimensions and weights Description Reference value Width 465mm Height 531.8mm Depth 249.5mm Case weight <40kg...
  • Page 19 4CAE000359 Disturbance Recording and Fault Locating Device DRL6600U Product version: V8.30 Issued: May 2017 Revision: - Table 7: analog input Description Reference value Frequency 50Hz ± 5Hz Linear operating range Voltage circuit: 0.1V...150V Current circuit: 0.1A…100A Analog input channel amount...
  • Page 20 4CAE000359 Disturbance Recording and Fault Locating Device DRL6600U Product version: V8.30 Issued: May 2017 Revision: - Table 9: Signal output Description Reference value Rated voltage 250V DC/AC Continuous current-carrying capacity 3 seconds current-carrying capacity 0.5 second current-carrying capacity Table 10: Data communication Ethernet port...
  • Page 21 4CAE000359 Disturbance Recording and Fault Locating Device DRL6600U Product version: V8.30 Issued: May 2017 Revision: - Table 14: Ambient test Description Type test Reference standard Cold test • Operation 16 hours at -10ºC IEC 60068-2-1/ANSI • Storage 16 hours at -25ºC C37.90-2006...
  • Page 22 4CAE000359 Disturbance Recording and Fault Locating Device DRL6600U Product version: V8.30 Issued: May 2017 Revision: - Description Type test value Reference standard Surge immunity test • Communication 1kV line to ground IEC 61000-4-5 • Other ports 2kV line to ground, 1kV line to...
  • Page 23 4CAE000359 Disturbance Recording and Fault Locating Device DRL6600U Product version: V8.30 Issued: May 2017 Revision: - Table 16: Insulation test Description Type test Reference standard Dielectric strength test • Test voltage 2kV, 50Hz, 1min IEC 60255-5 1kV, 50Hz, 1min, Impulse voltage test •...
  • Page 24 4CAE000359 Disturbance Recording and Fault Locating Device DRL6600U Product version: V8.30 Issued: May 2017 Revision: - Table 20: Parameters for disturbance recording and fault locating Name Value (range) Accuracy Settings ≥ 10%In, accuracy: ±10% Phase overcurrent 0.1…20A Negative-sequence Settings ≥ 10%In, accuracy: ±10% 0.05…20A...
  • Page 25: Ordering Information

    4CAE000359 Disturbance Recording and Fault Locating Device DRL6600U Product version: V8.30 Issued: May 2017 Revision: - 20. Ordering information Product Ordering code Description identification UAAEAL010100000B24AAAA DRL6600U DC110V UAAEAH010100000B24AAAA DRL6600U DC220V 32 AI (24I, 8U), 8 DC, 192 BI, GOOSE UAAEAL001010000B24AAAA...
  • Page 26 — ABB AB Grid Automation Products 721 59 Västerås, Sweden Phone: +46 (0) 21 32 50 00 abb.com/protection-control © Copyright 2017 ABB. All rights reserved. Specifications subject to change without notice.