Before you rack mount the appliance, you can ground it by using the grounding lugs provided.
To ground your IP2450 appliance
Note
Consult your company policy to determine the equipment grounding procedure that you use
with this unit installation.
1. Put on the wrist strap and attach the free end to the wrist-strap jack to the ESD grounding
plug on the front of the appliance.
2. Secure one end of the grounding cable to the side of the appliance either vertically or
horizontally, as shown in the figure, with the two 10-32 screws and kep washers included in
the grounding cable kit. Torque the screws to 80 inch ounces.
Note
The green/yellow insulated copper ground connector should be a minimum of #12 AWG
(minimum 2.5 mm
3. Use the 1/4-inch screw and kep washer included with the appliance or gateway to attach the
other end of the cable to the appliance or gateway rack-mount hardware (or other
appropriate earth ground location that meets the specifications of your installation site) with
the kep washer between the screw and cable lug. Torque the screw to 384 inch ounces
Check Point IP2450 Security Platform Installation Guide
Secure grounding-cable lug to rack or
other appropriate grounding location
with 1/4-inch screw and kep washer
Grounding lug can be positioned
either vertically or horizontally
or
2
cross-sectional areas).
Grounding cable
Attach cable lug to
side of appliance with
two 10-32 screws
Before You Begin
00646
31