Current Reversal Logic; Weak End Infeed Logic - ABB Relion 670 Series Commissioning Manual

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
Document
revision
F
G
H
J
K
L
M
11.11.2.2

Current reversal logic

It is possible to check the delay of the CS send signal with tDelayRev by changing from a reverse to a
forward fault.
By continuously activating the CR input and changing from a reverse to a forward fault, the delay
tDelayRev can be checked.
Checking of current reversal
1.
Set the healthy condition to an impedance at 50% of the reach of the reverse zone connected to
IRV.
2.
Activate the receive (CRL) signal.
3.
After the pickup condition is obtained for reverse zone, apply a fault at 50% of the reach of the
forward zone connected to WEIBLK2.
4.
Check that correct trip outputs and external signals are obtained for the type of fault generated. The
operation time should be about the tDelayRev setting longer than the carrier accelerated trip (TRIP)
recorded for the permissive overreach scheme communication.
5.
Restore the forward and reverse zone timer to its original setting.
11.11.2.3

Weak end infeed logic

Weak-end infeed logic at permissive overreach schemes
1.
Check the blocking of the echo with the injection of a CRL signal >40ms after a reverse fault is
applied.
2.
Measure the duration of the echoed CS signal by applying a CRL receive signal.
3.
Check the trip functions and the voltage level for trip by reducing a phase voltage and applying a
CRL receive signal.
190
Product
History
revision
2.2.3
-
2.2.3
-
2.2.3
-
2.2.4
-
2.2.4
-
2.2.4
2.2.5
Added DOs for teleprotection permissive (TxPrm & RxPrm1) transmit and receive signals in
accordance with 61850 Ed 2.0
The reverse zone timer must not operate before the forward zone fault is applied. The
user might need to block the reverse zone timer setting during testing of current reversal.
The forward zone timer must be set longer than the tDelayRev set value.
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 511 403-UUS Rev. K
M14947-8 v3
M14947-13 v9
M14947-37 v2
M14947-39 v5
Bay control REC670
Commissioning manual