Verifying The Back-Up Trip Mode - ABB Relion 670 Series Commissioning Manual

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
1.
Set RetripMode = Off.
2.
Apply the fault condition, including initiation of CCRBRF (50BF), well above the set current value.
3.
Verify that no re-trip, but back-up trip is achieved after set time.
4.
Disconnect AC and BFI_3P input signals.
Checking the re-trip with current check, RetripMode = UseFunctionMode
1.
Set RetripMode = UseFunctionMode.
2.
Apply the fault condition, including initiation of CCRBRF (50BF), well above the set current value.
3.
Verify that re-trip is achieved after set time t1 and back-up trip after time t2.
4.
Apply the fault condition, including initiation of CCRBRF (50BF), with current below set current
value.
5.
Verify that no re-trip, and no back-up trip is obtained.
6.
Disconnect AC and BFI_3P input signals.
Checking re-trip without current check
1.
Set RetripMode = Always.
2.
Apply the fault condition, including initiation of CCRBRF (50BF), well above the set current value.
3.
Verify that re-trip is achieved after the set time t1, and the back-up trip after time t2.
4.
Apply the fault condition, including initiation of CCRBRF (50BF), with current below set current
value.
5.
Verify that re-trip is achieved after set time t1, but no back-up trip is obtained.
6.
Disconnect AC and BFI_3P input signals.
11.4.9.6

Verifying the back-up trip mode

In the cases below it is assumed that FunctionMode = Current is selected.
Checking that back-up tripping is not achieved at normal CB tripping
Use the actual tripping modes. The case below applies to re-trip with current check.
1.
Apply the fault condition, including initiation of CCRBRF (50BF), with phase current well above set
value Pickup_PH.
2.
Interrupt the current, with a margin before back-up trip time, t2. It may be made at issue of re-trip
command.
3.
Check that re-trip is achieved, if selected, but no back-up trip is obtained.
4.
Disconnect AC and BFI_3P input signals.
The normal mode BuTripMode = 1 out of 3 should have been verified in the tests above. In applicable
cases the modes 1 out of 4 and 2 out of 4 can be checked. Choose the mode below, which corresponds
to the actual case.
Checking the case BuTripMode = 1 out of 4
It is assumed that the ground-fault current setting Pickup_N is below phase current setting Pickup_PH.
1.
Set BuTripMode = 1 out of 4.
2.
Apply the fault condition, including initiation of CCRBRF (50BF), with one-phase current below set
Pickup_PH but above Pickup_N . The residual ground-fault should then be above set Pickup_N.
3.
Verify that back-up trip is achieved after set time. If selected, re-trip should also appear.
4.
Disconnect AC and BFI_3P input signals.
106
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 511 403-UUS Rev. K
M12104-48 v8
M12104-58 v10
M12104-146 v5
M12104-150 v8
M12104-165 v6
Bay control REC670
Commissioning manual