Hardware Re-Configuration - ABB Relion 670 Series Commissioning Manual

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 403-UUS Rev. K
Headline
High CPU Load
Invaild parameter set for MIM
Mismatching data batch size to DistRep
LDCM missing connections
LDCM system frequency
LDCM AnalogLatency
HW Configuration missing
SMAI incorrect calculated phase-earth
14.2.4

Hardware re-configuration

When adding, removing or moving a hardware modules in an IED ( for example, I/O modules,
communication modules or time synchronization modules) a set of procedures must be followed.
Adding a new module in to an IED
Procedure:
1.
Switch the IED off and insert the new module.
2.
Switch the IED on, wait for it to start, and then perform a HW reconfig.
3.
Perform a license update in PCM600.
Bay control REC670
Commissioning manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Explanation
Total: 81.3%
Core0: 64.2 %
Core1: 98.4%
Tips to reduce the CPU load:
Configure minimum number of functional blocks
Switch off functional blocks not in use
Switch off protocols not in use
Remove IEC 61850 data sets not in use
Configure minimum communication data points
The IED prevented from applying the user settings for
IMinChx, IMaxChx, ValueMinch, ValueMaxCh as they
result in incorrect zero point calculation. Settings are
reverted to default values.
MIM:pX Channels:Channel_numbers
Check cycle time for SMAI and 3PHSUM blocks connected
to Disturbance Report blocks. SMAI and 3PHSUM blocks
shall have the same cycle time.
LDCM transmitter is missing connections. Check the
LDCMTRN block.
System frequency is different in local and remote end of
LDCM link.
Check the parameter FrequencySel at both ends.
LDCM analog latency is different in local and remote.
Check the LDCM parameters AnalogLatency and
remAinLatency at both ends.
HW configuration necessary to configure RSTP on
<Access Point> is missing. Please contact the SA - T
Supportline to fix this error.
Access points can be any of these : AP_1, AP_3
Calculated phase-earth values are used from one or more
SMAIs configured for phase-phase inputs, without
connected N input. However, this configuration, combined
with unbalanced three-phase input, will result in incorrectly
calculated phase-earth values. This in turn may result in
maloperation of functions connected to SMAIs configured
this way, if the function uses phase-earth based values.
Further, if SUM3PH is connected to such a SMAI, then its
output values will be incorrect, and connected functions
may maloperate. To remedy the situation, please revise the
configuration from this perspective.
Section 14
Troubleshooting
GUID-334C5D8B-F383-4CDE-9850-659ED6B405DC v1
233