1MRK 511 403-UUS Rev. K
11.4.9.2

Checking the phase current trip value, Pickup_PH

The check of the Pickup_PH current level is best made in FunctionMode = Current and BuTripMode = 1
out of 3 or 2 out of 4.
1.
Apply the fault condition, including BFI_3P of CCRBRF (50BF), with a current below set
Pickup_PH.
2.
Repeat the fault condition and increase the current in steps until a trip occurs. Note that the
INITIATE signal shall be re-applied for each new current value.
3.
Compare the result with the set Pickup_PH.
11.4.9.3
Checking the residual (ground fault) current trip value Pickup_N set below
Pickup_PH
Check the low set Pickup_N current where setting FunctionMode = Current and setting BuTripMode = 1
out of 4
1.
Apply the fault condition, including BFI_3P of CCRBRF (50BF), with a current just below set
Pickup_N.
2.
Repeat the fault condition and increase the current in steps until trip appears. Note that the
INITIATE signal shall be re-applied for each new current value.
3.
Compare the result with the set Pickup_N.
4.
Disconnect AC and BFI_3P input signals.
11.4.9.4

Checking the re-trip and back-up times

The check of the set times can be made in connection with the check of trip values above.
Choose the applicable function and trip mode, such as FunctionMode = Current and RetripMode =
UseFunctionMode.
1.
Apply the fault condition, including initiation of CCRBRF (50BF), well above the set current value.
Measure time from BFI_3P of CCRBRF (50BF).
2.
Check the re-trip t1 and back-up trip times t2 and t3.
In applicable cases, the back-up trip for multi-phase pickupt2MPh and back-up trip 2, t2 and t3 can
also be checked. To check t2MPh, a two-phase or three-phase initiation shall be applied.
3.
Disconnect AC and BFI_3P input signals.
11.4.9.5

Verifying the re-trip mode

Choose the mode below, which corresponds to the actual case.
In the cases below it is assumed that FunctionMode = Current is selected.
Checking the case without re-trip, RetripMode = Off
Bay control REC670
Commissioning manual
If RetripMode = Off and FunctionMode = Current is set, only backup trip can be used to
check set Pickup_PH.