FusionModule1000A20 CT Solution
Maintenance Guide
Figure 5-19 Removing a point-type water sensor
Step 3 Install a new water sensor and tighten the screws.
Step 4 Connect cables to the water sensor.
Step 5 Check that the new water sensor is working properly.
----End
Follow-up Procedure
Dispose of the removed water sensor that is confirmed faulty.
5.3.10 Replacing Access Control Components
5.3.10.1 Replacing an IC Card Reader
Prerequisites
Impact on the System
None
Preparations
Tools: Phillips screwdriver, protective gloves
Issue 01 (2019-02-25)
The gap between the water sensor and the floor is 2 mm.
Drip a small amount of water onto the water sensor. If the monitoring software terminal generates an
alarm, the water sensor is working properly.
An IC card reader needs to be replaced.
A spare IC card reader of the same model is available and functional.