FusionModule1000A20 CT Solution
Maintenance Guide
Alarm Name
AI/DI_1 wiring
error alarm
AI/DI_2 wiring
error alarm
AI/DI_3 wiring
error alarm
AI/DI_4 wiring
error alarm
AI/DI_5 wiring
error alarm
AI/DI_6 wiring
error alarm
3G module
communication
failure

4.3.2 Access Actuator Alarms

Alarm Name
Illegal door opening
Magnetic lock
overcurrent
IC card reader
removed
Account locked
Issue 01 (2019-02-25)
Alarm
Possible Cause
Severity
1. Sensor cables are
Major
2. The sensor type does
1. The 3G module is not
Major
2. The 3G module is
3. The 3G module is
Alarm
Possible Cause
Severity
Major
The door is open but no
card swiping or exit
button pressing is
detected.
Major
The power supply port of
the magnetic lock is
short-circuited.
Major
The IC card reader is
removed.
Informati
The account fails to pass
on
the authentication for 10
times.
Copyright © Huawei Technologies Co., Ltd.
incorrectly connected.
not match the specified
type.
connected properly.
faulty.
removed.
4 Alarms and Faults
Solution
1. Check the sensor cable
connection.
2. Check that the sensor
types on the WebUI
match the actual sensor
types.
1. Reconnect the PSU
properly.
2. Replace the 3G
module.
Solution
Check that the power
supply port of the
magnetic lock is not
short-circuited.
Check that the power
supply port of the
magnetic lock is not
short-circuited.
Check that IC card reader
is not removed.
Check that the account
fails to pass the
authentication for 10
times.
55