FusionModule1000A20 CT Solution
Maintenance Guide
1.
2.
3.
4.
Figure 5-25 Removing the emergency door release button
Step 2 Install a new emergency door release button.
1.
2.
3.
4.
Figure 5-26 Installing the emergency door release button
Step 3 Check that the new emergency door release button is working properly.
----End
Issue 01 (2019-02-25)
Remove screws securing the emergency door release button, as shown by (1) in Figure
5-25.
Remove the glass panel of the emergency door release button, as shown by (2) and (3) in
Figure 5-25.
Remove screws securing the base, as shown by (4) in Figure 5-25.
Disconnect cables and remove the emergency door release button.
Connect cables.
Tighten screws on the base, as shown by (1) in Figure 5-26.
Install the glass panel, as shown by (2) and (3) in Figure 5-26.
Tighten screws, as shown by (4) in Figure 5-26.
Remove the cover of the emergency door release button using a screwdriver, press the button, and rotate
the door handle clockwise to open the container door. If the door can be opened, the emergency door
release button is working properly.