FusionModule1000A20 CT Solution
Maintenance Guide
Categ
ory
ution
System
ECC80
0
WebUI
Issue 01 (2019-02-25)
Mainten
Operation
ance
Item
Check whether
the indicators are
normal.
Check whether
the ground points
properly connect
to the equipment
room ground bar.
PDC
Check the
luminance of the
indicators.
Check the SPD
indicator and
SPD circuit
breaker status.
FusionMo
On the ECC800
dule1000
WebUI, choose
alarms
Home > Active
Alarms or
Query >
Historical
Alarms.
Copyright © Huawei Technologies Co., Ltd.
Check
Troubleshooting
Standard
All indicators
Rectify the fault by
are normal.
referring to
TP48200B-N20B2 &
TP48200B-N20B3 &
TP48200B-L20B2 &
TP48400B-N20B3 &
TP48400B-L20B1
V500R002 User Manual.
The cable
Secure the ground point or
between the
replace the ground cable.
power system
ground point
and the
equipment room
ground bar is
securely
connected.
The three-phase
If an indicator is off or dim,
power indicators
replace it. For details, refer
are steady on.
to 5.1.2.5 Replacing an
Indicator.
The SPD
If the SPD indicator is red,
indicator is
replace the SPD. For
green.
details, refer to 5.1.2.4
Replacing an SPD.
1. If the SPD indicator is
The SPD circuit
breaker is
switched to ON.
2. Switch on the circuit
No alarm is
Refer to ECC800 Data
displayed in the
Center Controller
alarm
V100R001C30 User
information
Manual or iManager
area.
NetEco documentation.
Alarm short
Check whether the SIM
messages can be
card is properly installed. If
received.
the SIM card is faulty,
replace it by following
instructions in ECC800
Data Center Controller
V100R001C30 User
Manual.
3 Routine Maintenance
red, replace the SPD.
For details, refer to
5.1.2.4 Replacing an
SPD.
breaker.
17