2.
Tracing
Sampling starts according to the Pr.1020 and Pr.1024 settings.
The trace status can be monitored. (Refer to
3.
Waveform check
By using FR Configurator2, trace data stored in the internal RAM can be displayed on a computer screen. For
details, refer to the Instruction Manual of FR Configurator2.
 Selection of sampling time (Pr.1022, Pr.1023)
• The sampling time is determined by the sampling cycle and the number of data acquisition points. The the number of data
acquisition points varies depending on the setting in Pr.1023 Number of analog channels.
Pr.1023
Number of analog channels
1
2
3
4
5
6
7
8
page
Memory mode sampling time
Minimum (Pr.1022 = "1")
Maximum (Pr.1022 = "1000")
1704 ms
1704 s
1280 ms
1280 s
1024 ms
1024 s
852 ms
852 s
728 ms
728 s
640 ms
640 s
568 ms
568 s
512 ms
512 s
464.)
1704
1280
1024
852
728
640
568
512
Number of data
acquisition points
16. (A) Application Parameters
16.12 Trace function
11
12
13
14
15
16
17
18
19
20