NOTE
• Always calibrate the input after changing the voltage/current input specification with Pr.73 and Pr.267, and the voltage/current
input selection switch.
• Take caution when the following condition is satisfied because the inverter recognizes the deviation value as a negative
(positive) value even though a positive (negative) deviation is given: C42 (PID bias coefficient) > C44 (PID gain coefficient).
To perform a reverse action, set Pr.128 PID action selection to forward action. Alternatively, to perform a forward action,
set Pr.128 to reverse action. In this case, the PID output shutoff release level is (1000 - Pr.577).
Pr.934 < Pr.935 (normal setting)
Reverse action
Forward action
PID output shutoff release level
(Example) Set the following: C42 (Pr.934) = "500", C43 (Pr.934) = 20% (4 mA is applied), C44 (Pr.935) = "100", and C45
(Pr.935) = 100% (20 mA is applied).
When the set point = 400 and the measured value = 360, the deviation is +40 (>0), but the inverter recognizes the deviation
as -10% (<0). Because of this, operation amount does not increase in the reverse operation setting.
The operation amount increases when the forward operation is set.
To perform PID output shutoff release at deviation of +40 or higher, set Pr.577 = "960".
• The display of the following parameters is changed according to the C42 (Pr.934) and C44 (Pr.935) settings.
Pr.
131
PID upper limit
132
PID lower limit
133
PID action set point
553
PID deviation limit
577
Output interruption cancel level
 Changing the PID display coefficient of the LCD operation panel (FR-
LU08) or the parameter unit (FR-PU07) (Pr.759)
• Use Pr.759 PID unit selection to change the unit of the displayed value on the FR-LU08 or the FR-PU07. For the
coefficient set in C42 (Pr.934) to C44 (Pr.935), the units can be changed as follows.
434
16. (A) Application Parameters
16.5 Calibration of PID display
Reverse action setting to Pr.128
Forward action setting to Pr.128
Pr.577 - 1000
Set point
Deviation +40
Measured value
* ( ) indicates the deviation value
which the inverter can recognize
Name
Reverse action
Forward action
PID output shutoff release level
500
400
360
100
0
20%
(0%) (25%) (35%)
Deviation -10%
Pr.934 ≥ Pr.935
Forward action setting to Pr.128
Reverse action setting to Pr.128
1000 - Pr.577
100%
(100%)