Figure 8-18 Removing the monitoring board
Step 7 Install a new monitoring board.
Step 8 Install a new fuse.
Figure 8-19 Installing a new fuse
(1) Cover
Step 9 Reinstall the protective cover, communications cable, and DC power cable for the
general input unit.
Step 10 Turn on the upstream power distribution switch and input switch of the general
input unit.
Step 11 Log in to the ECC800-Pro WebUI, and choose Maintenance > Parameter Sync.
The parameter synchronization setting page is displayed.
Step 12 Click Device type and select the component type from the drop-down list.
Step 13 Select the failed device in Source Device, select the reserved device in Target
Device, and click Submit to synchronize the configuration parameters of the
failed device to the reserved device.
Step 14 On the Monitoring > System > ECC800 > Controls tab page, select Delete device
with communication failure, click Submit, and add the reserved device to the
smart module view.
Step 15 Check the running status of the general input unit to ensure normal
communication.
Issue 05 (2020-10-15)
Copyright © Huawei Technologies Co., Ltd.
(2) Fuse
8 Parts Replacement
65