Layout And Cable Routing Principles: Single-Row Aisle Containment (N+1 Scenario) - Huawei New Main Way 2.0 User Manual

Table of Contents

Advertisement

New Main Way 2.0
User Manual
Figure 3-5 Layout diagram
(1) General input unit
Figure 3-6 Cabling diagram
3.2.4 Layout and Cable Routing Principles: Single-Row Aisle
Containment (N+1 Scenario)
Issue 05 (2020-10-15)
The figures use single-phase power distribution units as an example.
The number of power distribution units allocated to each row of cabinets
must be an even number.
If the power density per cabinet is less than or equal to 10 kW, single-phase
power distribution units are used and each power distribution unit supports a
maximum of six IT or network cabinets. One power distribution unit provides
six power outputs to route A, and the other power distribution unit provides
six power outputs to route B for the corresponding cabinets.
If the power density per cabinet is greater than 10 kW, three-phase power
distribution units are used and each power distribution unit supports a
Copyright © Huawei Technologies Co., Ltd.
(2) Power distribution unit
3 Installation
(3) Aisle containment
20