Step 3 Determine the position of the general input unit or power distribution unit in the
plan view of the WebUI.
Press the Blink button on the general input unit or power distribution unit for less
than 1s to report the blinking status to the ECC800-Pro. The corresponding device
icon in the plan view of the WebUI blinks.
Step 4 You are advised to change the device name. For example, change the Device
name of the power distribution unit to be the same as that on the label attached
to the power distribution unit, for example, NMW A 01.
----End
Issue 05 (2020-10-15)
Path
Parameter Name
QF1 Branch circuit breaker
in use (L1)
QF2 Branch circuit breaker
in use (L2)
Upper load current
threshold
Lower load current
threshold
Set the parameters for other power distribution units in the same way or by
synchronizing parameters.
Path: Maintenance > Parameter Sync
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Defaul
Description
t Value
Enable
When the
parameter is set to
Disable for a
branch, all alarms of
the branch will not
be reported.
When the
parameter is set to
Enable for a branch,
all alarms of the
branch will be
reported.
80
When the load
current exceeds the
preset value, an
alarm is generated.
60
When the load
current exceeds the
preset value, an
alarm is generated.
47