Layout And Cable Routing Principles: Dual-Row Aisle Containment (2N Scenario) - Huawei New Main Way 2.0 User Manual

Table of Contents

Advertisement

New Main Way 2.0
User Manual
Figure 3-4 Cabling diagram
3.2.3 Layout and Cable Routing Principles: Dual-Row Aisle
Containment (2N Scenario)
Issue 05 (2020-10-15)
Figure 3-3 Layout diagram
(1) General input unit (2) Power distribution
There are two routes of NMWs, routes A and B, for each row of cabinets. The
number of power distribution units deployed on each route of the NMW
should be the same.
If the power density per cabinet is less than or equal to 10 kW, single-phase
power distribution units are used and each power distribution unit supports a
maximum of six IT or network cabinets. One power distribution unit provides
six power outputs to route A, and the other power distribution unit provides
six power outputs to route B for the corresponding cabinets.
If the power density per cabinet is greater than 10 kW, three-phase power
distribution units are used and each power distribution unit supports a
maximum of two IT or network cabinets. One power distribution unit provides
two power outputs to route A, and the other power distribution unit provides
two power outputs to route B for the corresponding cabinets.
Copyright © Huawei Technologies Co., Ltd.
(3) Aisle containment (4) Cross-row cable
unit
3 Installation
tray
19