Port
L3
N
PE
Power Distribution Unit
Table 3-3 Recommended cross-sectional areas for three-phase output power
cables
Output Switch
Recommended
cross-sectional
area (mm
Table 3-4 Recommended cross-sectional areas for single-phase output power
cables
Output Switch
Recommended
cross-sectional
area (mm
Issue 05 (2020-10-15)
Connection
Method
Crimped DT
terminal
Crimped DT
terminal
Crimped DT
terminal
L1
L2
2
)
L3
N
PE
L
N
2
)
PE
When selecting, connecting, and routing power cables, follow local safety
regulations and rules.
When the external conditions such as cable routing mode or ambient
temperature change, perform verification in accordance with the IEC
60364-5-52 or the local regulations.
The cables listed in the tables are used only when the following requirements
are met:
Copyright © Huawei Technologies Co., Ltd.
Bolt
Specifications
250
400
A/3P
A/3P
M12
M12
M10
M12
16 A/3P
40 A/3P
5 x 6
5 x 6
16 A/1P
3 x 6
3 Installation
Recommended Bolt
Length
250 A/3P
400 A/3P
25 mm
35 mm
63 A/3P
5 x 10
40 A/1P
63 A/1P
3 x 6
3 x 10
16