Table 7-1 General input unit alarm reference
Alarm ID
Alarm Name
412177004
General input unit and
ECC800
communication failure
412177000
POE1/POE2/POE3/
-41217700
POE4 output overload
3
412177005
Detection board
abnormal
412177006
L1/L2/L3 open-phase
-41217700
8
Issue 05 (2020-10-15)
Alarm
Severity
Critical
Major
Critical
Critical
Copyright © Huawei Technologies Co., Ltd.
7
Possible Causes
Communication with
the PoE module is
interrupted.
The output is
overloaded or the
power supply pin is
short-circuited.
The monitoring board
hardware is faulty.
Phase voltage is
below the open-phase
threshold.

7 Alarm List

Alarm List
Procedure
Check the cable
connection to the
general input unit.
● Check whether the
output is
overloaded.
● Check that the
power supply pin is
not short-circuited.
● Check that no
other alarm is
generated for the
monitoring board.
● Replace the
monitoring board.
● Check the power
input.
● Use the power
supply with a
normal input
voltage.