  • Page 1 PDC-0038V4ACIOA V100R001 Quick Installation Guide Issue: 01 Part Number: 31505549 Date: 2013-05-15 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Huawei equipment, in addition to following the general precautions in this document, follow the specific safety instructions given by Huawei. Huawei will not be liable for any consequences that are caused by the violation of safety regulations and design, production, and usage standards.
  • Page 3 Appearance PDC-0038V4ACIOA PDC is short for power distribution cabinet. UPS is short for uninterruptible power system. PDU Model PDC-0038V4ACIOA Applicable UPS UPS2000-G-15KRTL/20KRTL Weight 15 kg Dimensions 130 mm x 430 mm x 585 mm (H x W x D) Front panel (under the cover) 1.
  • Page 4: Unpacking And Checking

    Check the PDU bar code and ensure that it complies with the order. Check against the delivery list that the types of fittings are complete and correct. If there is any discrepancy, contact your local Huawei office immediately. Device Movement Regulations Do not move the PDU by holding its mounting brackets, front panel, or terminal cover.When you move it, see the movement...
  • Page 5: Mechanical Installation

    Mechanical Installation Rack-mounting the PDU This document uses a 19-inch rack as an example. For other racks, see the related UPS quick installation guide. Install mounting brackets. Install adjustable guide rails and floating nuts. 1. Install adjustable guide rails when you rack-mount a device. For a 2 U device, install only adjustable guide rails and secure it with screws.
  • Page 6 Place the PDU on the guide rails. Secure the PDU to the rack using M6x16TM screws through the holes in the mounting brackets. Do not move the PDU by holding its mounting brackets, front panel, or terminal cover.When you move it, see the movement regulations.
  • Page 7: Cable Installation

    Assemble support bases. When you assemble two support bases, align connecting buckles with holes and insert the buckles vertically, as shown in the following figure. Install two support bases for each group of devices. Place the support bases on the floor, determine the distance (greater than or equal to 280 mm) between the support bases, place devices on the support bases, and secure them.
  • Page 8 Loosen screws to remove the busbar cover. Connect cables. Connecting Cables to the PDU for a 1+1 UPS2000-G-15 kVA/20 kVA Parallel System (Three-Phase Input Three- Phase Output)  Torque for tightening power cables Device Tool Screw Torque UPS2000-G-15 kVA M5x0.8p 1.5 N·m UPS2000-G-20 kVA M5x0.8p...
  • Page 9 No. Item Appearance Specifications Remarks Prepared PDU AC output 6 mm² power cable onsite PDU bypass Prepared input power 6 mm² onsite cable PDU mains input Prepared 6 mm² power cable onsite UPS 1 bypass Delivered input power with the cable UPS 1 mains Delivered...
  • Page 10: Power-On Procedure

    Mapping between cable connectors for CAN communications ports.  Cable connection diagram MBS is short for maintenance bypass switch. The preceding figure shows how to connect cables when there are two mains inputs. In the case of one mains input, connect the mains input power cables to the AC BYPASS INPUT ports (the AC MAINS INPUT ports are not connected).
  • Page 11 Appendix Maintenance bypass usage 1. UPS 1 mains input circuit 2. UPS 2 mains input circuit 3. UPS 1 bypass input circuit breaker 4. UPS 2 bypass input circuit breaker breaker breaker 5. UPS 1 output circuit 6. UPS 2 output circuit breaker 7.