FusionModule2000 Smart Modular Data Center
Product Description (380 V)
3.7 Surge Protection and Grounding System
The surge protection and grounding system of the smart module consists of the surge
protection solution and grounding solution.
3.7.1 Surge Protection Solution
The smart module uses the following surge protection solution.
SPDs are installed in front of the target equipment. The conducting wires to each SPD are
short (within 0.15 m) and straight. The SPD wires are copper wires with a minimum
cross-sectional area of 10 mm
minimum cross-sectional area of 16 mm
3.7.2 Grounding Solution
Solution 1: M-shaped (Grid) Grounding (Recommended)
Figure 3-94 M-shaped (grid) grounding solution for a single-row aisle containment
Figure 3-95 M-shaped (grid) grounding solution for a dual-row aisle containment
Issue 04 (2017-06-30)
2
, and the ground cables to SPDs are copper cables with a
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2
.
3 System Architecture
131