FusionModule2000 Smart Modular Data Center
Product Description (380 V)
Indicato
r
ALM
RF_Z
Communications Ports
The access actuator provides one DO port (LOCK/GND) and one DI port (GATE/GND).
Table 3-71 lists the LOCK/GND/GATE/GND port pin definitions.
Table 3-71 LOCK/GND/GATE/GND port pin definitions
Item
LOCK/GND
(control
magnetic
locks) pin
sequence
GATE/GND
(door status)
pin sequence
Issue 04 (2017-06-30)
Color
Name
Red
Alarm
indicator
Green
Wireless
communicati
on status
indicator
Description
LOCK
12V_OUT
GND
GND
GATE
DI1
GND
GND
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Status
Description
Blinking
The indicator blinks at super
short intervals for 0.5s (blinking
at 10 Hz, on for 0.05s and then
off for 0.05s) and then turns off
for 0.5s. The cycle lasts for 10s.
Steady on
A system failure alarm is
generated.
Off
No system alarm is generated.
Steady on
No network parameters exist, or
a network is to be created.
Blinking at
A network is set up, and no
long intervals
node access is allowed (the
indicator blinks at 0.5 Hz, on for
1s and then off for 1s).
Blinking at
A network is set up, and node
super short
access is allowed (the indicator
intervals
blinks at 10 Hz, on for 0.05s
and then off for 0.05s).
Blinking
The access actuator is searching
intermittently
for a network (the indicator
at super short
blinks at super short intervals
intervals
for 0.5s and then turns off for
0.5s).
3 System Architecture