3.1.5 Skylight

A skylight is used for sealing an aisle containment. There are three types of skylights: control
skylight, rotating skylight, and flat skylight. Table 3-3 lists the technical specifications of
skylights and the mapping between skylights and cabinets.
Table 3-3 Technical specifications of skylights
Name
Control skylight
Issue 04 (2017-06-30)
Specifications
Black
High-intensity class A carbon cold rolled steel plate and
zinc-coated steel plate
Front and rear air channels
A 2000 mm high cabinet provides 42 U available space.
A 2200 mm high cabinet provides 47 U available space.
The distance between the front and rear mounting bars
can be adjusted for every 25 mm. Positions for vertically
installing two PDU2000s are provided at the rear of the
cabinet.
Installed on a concrete floor, a base, or an ESD floor
The front door is a single door, and the rear door is a double
one.
2000 mm x 600 mm x 1200 mm: 128 kg
2000 mm x 800 mm x 1200 mm: 153 kg
2200 mm x 600 mm x 1200 mm: 137 kg
2200 mm x 800 mm x 1200 mm: 164 kg
2000 mm x 600 mm x 1100 mm: 110 kg
2000 mm x 800 mm x 1100 mm: 135 kg
IP20
Dimensions (H x W x D)
341 mm x 605 mm x 1334 mm
341 mm x 805 mm x 1334 mm
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 System Architecture
Applicable Cabinet
Dimensions (H x W x D)
2000 mm x 600 mm x 1200
mm
2000 mm x 600 mm x 1100
mm
2200 mm x 600 mm x 1200
mm
2000 mm x 800 mm x 1200
mm
2000 mm x 800 mm x 1100
13