Starting ACS380 drives for PROFINET

1. Power up the drive.
2. Enable the communication between the adapter module and the drive by setting parameter 50.01
FBA A Enable to Enable.
3. With parameter 50.02 FBA A comm loss func, select how the drive reacts to a fieldbus
communication break.
Note: This function monitors both communication between the fieldbus master and the adapter
module and communication between the adapter module and the drive.
4. With parameter 50.03 FBA A comm loss t out, define the time between communication break
detection and the selected action.
5. Select application-specific values for the rest of the parameters in group 50, starting from 50.04.
6. Set the FPBA-01 configuration parameters in group 51. At the minimum, set the required node
address in parameter 51.02 Node address and the communication profile in 51.05 Profile = 1 (ABB
drives).
7. Define the process data transferred to and from the drive in FBA-01 configuration parameter groups
52 and 53.
Note: The adapter module sets the Status word and Control word automatically in parameters 52.01
FBA A data in1 and 53.01 FBA data out1.
8. Validate the settings made in parameter groups 51, 52 and 53 by setting parameter 51.27 FBA par
refresh to Configure.
9. Save the valid parameter values to permanent memory by setting parameter 96.07 Param save
manually to Save.
10. Set the relevant drive control parameters to control the drive according to the application.

ACS380 Minimum required parameter settings for PROFINET

The minimum required parameter settings based on factory default settings.
Parameter
Description
50.01
FBA A Enable
51.01
FBA A ype
51.02
Protocol/Profile
51.04
IP Configuration
51.05 ...
IP address
51.08
51.09
Subnet CDR
51.27
FBA PAR REFRESH
52.02
FBA data in2
53.02
FBA data out2
Setting
Enable
Ethernet
PNIO ABB Pro (11)
Static (0)
192.xxx.xx.xx or any
other required IP
address.
24
REFRESH
Act1 16bit (5)
Ref1 16bit (2)
Comment
Activates fieldbus module
Filedbus type
Communication profile ABB drives
-
-
24 For subnet mask 255.255.255.0
Updates fieldbus settings (groups 51 to 55)
Actual speed as Data Word 2 from the drive
Speed reference as Data Word 2 to the drive