ACS880 Minimum required parameter settings for PROFIBUS DP

The minimum required parameter settings based on factory default settings.
Parameter
Description
50.01
FBA A Enable
51.02
NODE ADDRESS
51.05
PROFILE
52.02
FBA data in2
53.02
FBA data out2
51.27
FBA par refresh
20.01
Ext 1 commands
22.11
Speed ref1
selection
31.11
Fault reset
selection
(46.01)
Speed scaling
Setting
Comment
Enable
Activates fieldbus module.
[PB NODE]
PROFIBUS DP node address of the drive.
1
Communication profile ABB drives.
Act1 16bit (5)
Actual speed as Data Word 2 from the drive.
Ref1 16bit (2)
Speed reference as Data Word 2 to the drive.
Configure
Updates fieldbus settings (groups 50 to 57).
Fieldbus A
Fieldbus interface as source for start and stop.
FB A ref1
Fieldbus interface as source for speed reference.
P.06.01 bit 7
Fieldbus interface as source for fault reset.
[Scale max]
Max speed/frequency scaling value (used in function
block/visualization input SPEED_REF_MAX). Must be
less or equal to drive parameter max speed/frequency.