Configuring ACS355 drives

Starting ACS355 drives for PROFIBUS DP

1. Power up the drive.
2. Enable the communication between the adapter module and the drive by setting parameter 98.02
COMM PROT SEL to EXT FBA.
3. Set the FPBA-01 configuration parameters in group 51. At the minimum, set the required node
address in parameter 51.02 and the communication profile in 51.05 = 1 (ABB drives).
4. With parameter 30.18 COMM FAULT FUNC, select how the drive reacts to a fieldbus communication
break.
5. With parameter 30.19 COMM FAULT TIME, define the time between communication break detection
and the selected action.
6. Define the process data transferred to and from the drive in the FBA-01 configuration parameter
groups 54 and 55.
Note: The adapter module sets the Status word and actual value automatically in parameters 54.01
and 54.02, and Control word and reference in parameters 55.01 and 55.02.
7. Validate the settings made in parameter groups 51, 54 and 55 by setting parameter 51.27 FBA PAR
REFRESH to REFRESH.
8. Set the relevant drive control parameters to control the drive according to the application.

ACS355 Minimum required parameter settings for PROFIBUS DP

The minimum required parameter settings are based on factory default settings.
Parameter
Description
98.02
COMM PROT
SEL
51.02
NODE ADDRESS
51.05
PROFILE
51.27
FBA PAR
REFRESH
10.01
EXT 1
COMMANDS
11.03
REF1 SELECT
16.04
FAULT RESET
SEL
(11.05)
REF1 MAX
Setting
Comment
EXT FBA
Activates fieldbus module.
[PB NODE]
PROFIBUS DP node address of the drive.
1
Communication profile ABB drives.
REFRESH
Updates fieldbus settings (groups 51 to 55).
COMM
Fieldbus interface as source for start and stop.
COMM
Fieldbus interface as source for speed reference.
COMM
Fieldbus interface as source for fault reset.
[Scale max]
Max speed/frequency scaling value (used in function
block/visualization input SPEED_REF_MAX). Must be less
or equal to drive parameter max speed/frequency.