Starting up ACS310 drives with embedded Modbus RTU 
Minimum required parameter settings (based on factory default settings) 
Parameter  Description 
98.02 
COMM PROT SEL 
53.02 
EFB STATION ID 
53.03 
EFB BAUD RATE 
53.04 
EFB PARITY 
53.05 
PROFILE 
Drive power down and power up for the new fieldbus settings to take effect! 
10.01 
EXT 1 COMMANDS 
11.02 
EXT1/EXT2 SEL 
11.03 
REF1 SELECT 
16.04 
FAULT RESET SEL 
 
Optional parameter settings 
30.18 
COMM FAULT 
FUNC 
30.19 
COMM FAULT TIME  [optional] 
(11.05) 
REF1 MAX 
 
Modbus RTU 
Setting 
Comment 
STD 
Activates fieldbus communication 
MODBUS 
[Address] 
Modbus RTU node address of the drive 
19.2 kbit/s 
Transfer rate of the link. Same baud rate must be 
(example) 
defined in the Modbus RTU master. 
8 NONE 1 
Parity and stop bits. Same parity and stop bits must 
(example) 
be defined in the Modbus RTU master. 
ABB DRV 
Communication profile "ABB Drives" 
FULL 
COMM 
Fieldbus interface as source for start and stop 
COMM 
Fieldbus interface as source to switch to EXT2 
COMM 
Fieldbus interface as source for speed reference 
COMM 
Fieldbus interface as source for fault reset 
[optional] 
How the drive reacts to a fieldbus communication 
break. 
Time between communication break detection and 
the selected action. 
[Scale max]  Max speed/frequency scaling value (used in function 
block/visualization input "SPEED_REF_MAX"). Must 
be less or equal to drive parameter max 
speed/frequency. 
‐ 14 ‐ 
 
 