ACSM1 Minimum required parameter settings for PROFIBUS DP

The minimum required parameter settings based on factory default settings.
Parameter
Description
50.01
FBA ENABLE
51.02
NODE ADDRESS
51.05
PROFILE
52.01
FBA DATA IN1
52.02
FBA DATA IN2
53.01
FBA DATA OUT1
53.02
FBA DATA OUT2
51.27
FBA PAR
REFRESH
10.01
EXT1 START
FUNC
24.01
SPEED REF1
SEL
10.08
FAULT RESET
SEL
(25.02)
SPEED SCALING
Setting
Comment
Enable
Activates fieldbus module.
[PB NODE]
PROFIBUS DP node address of the drive.
1
Communication profile ABB drives.
4
Status word as Data Word 1 from the drive.
5
Actual speed as Data Word 2 from the drive.
1
Control word as Data Word 1 to the drive.
2
Speed reference as Data Word 2 to the drive.
REFRESH
Updates fieldbus settings (groups 50 to 53).
FBA
Fieldbus interface as source for start and stop.
FBA REF1
Fieldbus interface as source for speed reference.
P.02.12 bit 8
Fieldbus interface as source for fault reset.
[Scale max]
Max speed/frequency scaling value (used in function
block/visualization input SPEED_REF_MAX). Must
be less or equal to drive parameter max
speed/frequency.