Mitsubishi Electric A800 Plus Series Function Manual page 145

Hide thumbs Also See for A800 Plus Series:
Table of Contents

Advertisement

Parameter setting procedure for tension sensorless torque control
9
Actual line speed input
Use Pr.362 to select the input terminal for actual line speed.
Pr.
362
Actual line speed input selection
∗1
To perform Vector control, install the Vector control compatible option.
∗2
The input specification in the initial setting is indicated. (Refer to
The following table shows setting examples.
Item
Actual line
speed input
method
Parameter
setting
144
TENSION SENSOR FEEDBACK TORQUE CONTROL
Name
0 (initial value)
1
2
3
4
5
6
7
9999
Setting example 1
Setting by analog current (4 to 20 mA) input
through terminal 4 (Pr.362 = "4")
Actual line speed
Pr.279
(Maximum line speed)
Pr.281
(0 m/min)
4 mA
Pr.280
(20%)
Analog input value
Pr.280 Actual line speed voltage/current bias =
20%
Pr.281 Actual line speed bias = 0 m/min
Pr.278 Actual line speed voltage/current gain =
100%
Pr.279 Actual line speed gain = Maximum line
speed
Setting
V* (line speed command)
Terminal JOG single-phase pulse train input (Refer to
164)
FR-A8AP/FR-A8AL/FR-A8TP encoder pulse train input
(complementary 12 V / differential 5 V (A-, B-phases))
(Refer to
page
Terminal 2 (analog value: 0 to 100%) (0 to 5 VDC)
page
165)
Terminal 4 (analog value: 20 to 100%) (4 to 20 mADC)
(Refer to
page
Terminal 1 (analog value: -100 to 100%) (0 to ±10 VDC)
(Refer to
page
Terminal 6 (FR-A8AZ) (analog value: -100 to 100%) (0 to ±10
VDC)
(Refer to
∗2
FR-A8AL single-phase pulse train input (PP, NP) (Refer to
page
164)
No function
page
43.)
Setting by pulse train input through terminal JOG
(Pr.362 = "1")
(Maximum line speed)
20 mA
Pr.278
(100%)
Pr.384 Input pulse division scaling factor ≠ "0"
Pr.281 Actual line speed bias = 0 m/min
Pr.282 Actual line speed pulse input bias = 0 kpps
Pr.279 Actual line speed gain = Maximum line
speed
Pr.283 Actual line speed pulse input gain =
Maximum number of pulses
Input terminal
164)
165)
165)
page
165)
Setting example 2
Actual line speed
6553.4
Pr.279
Pr.281
(0 m/min)
Pr.282
Pr.283
(Maximum number
(0 kpps)
of pulses)
Number of input pulses
page
∗1
(Refer to
∗2
∗2
∗2