Ex relevant specifications
7.3.5

IECEx n

Electrical data for TZIDC-120 designated as Ex nA IIC T6 or T4 Gc
Signal circuit
(terminal +11 / -12)
Mechanical digital feedback
(terminal limit1 +51 / -52 or limit2 +41 / -42)
Plug-in module for shutdown contact input
(terminal +51 / -52 or +85 / -86)
Special conditions
Devices may only be connected to circuits in zone 2 if they are suitable for operation in zone
2 potentially explosive atmospheres and for the conditions prevailing at the installation
location (manufacturer's declaration or certificate from an inspection authority).
For the "digital feedback with proximity switches" circuit, external measures must be
implemented to prevent the rated voltage from being exceeded by more than 40 % in the
event of transient disturbances.
It is only permissible to connect, disconnect, and switch live circuits during installation or
maintenance, or for the purpose of carrying out repairs. Comment: It is considered very
unlikely that a potentially explosive atmosphere would be present in zone 2 at the same time
that installation or maintenance/repair work was being carried out.
Only non-flammable gases may be used for the pneumatic auxiliary power.
Only use suitable cable entries which meet the requirements of IEC 60079-15.
If the SJ2_S1N (NO) proximity switch is used, the positioner may only be operated at an
ambient temperature range from -25 ... 85 °C.
62
TZIDC, TZIDC-110, TZIDC-120
U = 9 ... 32 V DC
I = 11.5 mA
U = 5 to 11 V DC
U = 20 ... 30 V DC
CI/TZIDC/110/120-EN