Use In Potentially Explosive Atmospheres In Accordance With Atex And Iecex; Product Identification; Ex Marking; Mounting - ABB PositionMaster EDP300 Manual

Digital positioner
Hide thumbs Also See for PositionMaster EDP300:
Table of Contents

Advertisement

6
PositionMaster EDP300 DIGITAL POSITIONER | CI/EDP300-EN REV. D
2 Use in potentially explosive atmospheres in accordance with
ATEX and IECEx
Change from one to two columns
Note
Further information on the Ex-Approval of devices can be found
in the type examination certificates or the relevant certificates
at www.abb.com/positioners.

Product identification

Depending on the type of explosion protection, an Ex name plate
is attached next to the main name plate on the positioner.
This indicates the level of explosion protection and the device's
relevant Ex certificate.

Ex marking

ATEX
Type Examination Test Certificate
II 1G Ex ia IIC T6 or T4 Ga
II 1D Ex iaD IIIC T55°C or T100°C Da
Ta = −40°C to 40°C or 85°C
II 3G Ex nA IIC T6 or T4 Gc
II 2D Ex tb IIIC T55°C or T100°C Db
Ta = 40°C to 40°C or 80°C
IECEx
Type Examination Test Certificate
Ex ia IIC T6 or T4 Ga
Ex iaD IIIC T55 °C or T100°C Da
Ta = −40 ° to 40 ° or 85 °C
Ex nA IIC T6 or T4 Gc
Ex tb IIIC T55 °C or T100°C Db
Ta = −40 ° to 40 ° or 80 °C
EAC TR-CU-012
Ex ia IIC T4/T6 Ga X
Ex ia IIIC T100°C/T55°C Da IP65
EX nA IIC T4/T6 Gc X
Ex tb IIIC T100°C/T55°C Db IP65

Mounting

The installation, commissioning, maintenance and repair of
devices in potentially explosive atmospheres must only be
carried out by appropriately trained personnel. Works may be
carried out only by persons, whose training has included
instructions on different types of protection and installation
techniques, concerned rules and regulations as well as general
principles of zoning. The person must possess the appropriate
competences for the type of work to be conducted.
When operating with combustible dusts, comply with
EN 60079-31.
The safety instructions for electrical apparatus in potentially
explosive areas must be in accordance with Directive
2014/34/EU (ATEX) and IEC 60079-14 (Installation of electrical
equipment in potentially explosive areas).
Comply with the applicable regulations for the protection of
employees to ensure safe operation.
ZELM 11 ATEX 0456 X
Note
Observe the device's applicable specifications and special
conditions in accordance with the type examination certificate
or other certificates!
Any manipulation in the device by users is not permitted.
Only the manufacturer or an explosion protection specialist
may modify the device
The device may only be operated using instrument air that is
IECEx ZLM 11.0001 X
free from oil, water and dust.

Cable gland

Limited temperature range of the M20 × 1.5 plastic cable gland
for explosion protection variants.
The permissible ambient temperature range of the cable gland is
−20 to 80 °C (−4 to 176 °F). When using the cable gland, make
sure that the ambient temperature is within this range. The
cable gland must be installed in the housing with a tightening
torque of 3.8 Nm. When installing the connection of the cable
gland and cable, check for tightness to ensure that the required
IP rating is met.