Commissioning
If Autoadjust is successful, the parameters will be stored automatically and the positioner will
revert to operating mode 1.1.
If an error occurs during Autoadjust, the process will be terminated with an error message. If
this happens, press and hold down
to the operating level, mode 1.3 (manual adjustment within the sensor range). The mount is
checked and corrected if necessary. Autoadjust then runs again.
6. Set potential dead band and tolerance band
This step is only required for critical (e.g., very small) actuators. It is not necessary under
normal circumstances.
1) The zero position is determined automatically and saved during Autoadjust (counter-clockwise (CTCLOCKW) for
linear actuators and clockwise (CLOCKW) for rotary actuators).
6.2.1

Operating modes

Selection from the operating level:
Press and hold down
Press and release
Release
The position is displayed in % or as a rotation angle
Operating mode
1.1
Positioning with fixed setpoint
Use
1.2
Manual adjustment
Adjust with
1.3
Manual adjustment
Adjust with
1) Positioning not active.
2) for high-speed mode: Press
34
as often as required to display the selected operating mode
or
to adjust the setpoint
1)
in the operating range
2)
or
1)
in the sensor range
2)
or
and
TZIDC, TZIDC-110, TZIDC-120
or
for approximately three seconds. The unit will switch
Mode indicator
conf
conf
conf
simultaneously.
Position indicator
°
C
%
mA
conf
°
C
%
mA
conf
°
C
%
mA
conf
CI/TZIDC/110/120-EN
°
C
%
mA
°
C
%
mA
°