Ex relevant specifications
Model TZIDC, P/N V18345-x0x2x2xx0x Intelligent Positioner
Input rated
Max output pressure
Max. ambient
Class I, Div 1, Groups A, B, C and D;
Class II, Div 1, Groups E, F and G
Class III, Enclosure Type 4X:
Model TZIDC, P/N V18345-x0x2x2xx0x Intelligent Positioner intrinsically safe with entity
parameters of:
Terminals 11 / 12
Terminals 81 / 82
Terminals 83 / 84
Terminals 31 / 32
Terminals 41 / 42 and
51 / 52
Terminals Limit2 41 / 42 and
Limit1 51 / 52
When installed per installation Drawing No 901064
Temperature Code
Max. Ambient
IMPORTANT (NOTE)
The "x" in P/N denotes minor mechanical variations or optional features.
Do not use the local communication interface (LKS) in hazardous areas.
Each pair of conductors for each intrinsic safety circuit must be shielded.
42
V max = 30 V
I max = 104 mA
C
= 6.6 nF
i
L
= 0 uH
i
V max = 30 V
I max = 110 mA
C
= 4.2 nF
i
L
= 0 uH
i
V max = 30 V
I max = 90 mA
C
= 4.2 nF
i
L
= 0 uH
i
V max = 30 V
I max = 110 mA
C
= 6.6 nF
i
L
= 0 uH
i
V max = 30 V
I max = 96 mA
C
= 3.7 nF
i
L
= 0 uH
i
V max = 15.5 V
I max = 52 mA
C
= 20 nF
i
L
= 30 uH
i
TZIDC, TZIDC-110, TZIDC-120
30 V DC; max. 4 ... 20 mA
90 psi
85 Deg C
T4
85 Deg C
CI/TZIDC/110/120-EN