ABB TZIDC Operating Instructions Manual

ABB TZIDC Operating Instructions Manual

Electro-pneumatic positioner
Table of Contents

Advertisement

Operating Instruction
42/18-84-EN
Electro-Pneumatic Positioner
TZIDC, TZIDC-110, TZIDC-120
for 4 ... 20 mA two-wire technology,
HART, PROFIBUS PA,
FOUNDATION Fieldbus

Advertisement

Table of Contents
loading

Summary of Contents for ABB TZIDC

  • Page 1 Operating Instruction Electro-Pneumatic Positioner 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120 for 4 ... 20 mA two-wire technology, HART, PROFIBUS PA, FOUNDATION Fieldbus...
  • Page 2 Fax: +49 621 381 931-29031 automation.service@de.abb.com © Copyright 2011 by ABB Automation Products GmbH Subject to changes without notice This document is protected by copyright. It assists the user in safe and efficient operation of the device. The contents of this document, whether whole or in part, may not be copied or reproduced without prior approval by the copyright holder.
  • Page 3: Table Of Contents

    4.2.2 Mounting on linear actuators.........................17 4.2.3 Mounting on rotary actuators ........................21 Electrical connections ..........................24 Screw terminal assignments ........................25 Jumper configuration on mainboard (TZIDC-120 only)................26 Cable entry ..............................27 Setting the mechanical feedback .........................27 5.4.1 Mechanical position indicator........................27 5.4.2 Mechanical digital feedback with proximity switches ................28 5.4.3...
  • Page 4 EC type-examination test certificate .....................60 10.2.2 IECEx Issue No. 3..........................61 10.2.3 CSA International ..........................63 10.2.4 CSA Certification Record ........................64 10.2.5 FM Approvals ............................65 10.2.6 FM Control Document ...........................66 10.3 TZIDC-120..............................69 10.3.1 EC type-examination test certificate .....................69 TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 5 FM Control Document ...........................75 Parameter descriptions ..........................78 11.1 TZIDC ................................78 11.1.1 Parameter overview ..........................78 11.1.2 Parameter description ...........................79 11.2 TZIDC-110 / TZIDC-120..........................81 11.2.1 Parameter overview ..........................81 11.2.2 Parameter description ...........................82 Appendix ..............................83 12.1 Other applicable documents.........................83 12.2 Approvals and certifications .........................83 Index ................................86...
  • Page 6: Safety

    Intended use TZIDC, TZIDC-110, TZIDC-120 positioners are electro-pneumatic positioning devices for use with pneumatically controlled actuators. The device may only be used for the applications listed in these operating instructions and in the data sheet.
  • Page 7: Target Groups And Qualifications

    Prior to using corrosive and abrasive materials for measurement purposes, the operator must check the level of resistance of all parts coming into contact with the materials to be measured. ABB Automation Products GmbH will gladly support you in selecting the materials, but cannot accept any liability in doing so.
  • Page 8: Plates And Symbols

    Failure to observe this safety information may result in damage to or destruction of the product and/or other system components. IMPORTANT (NOTE) This symbol indicates operator tips, particularly useful information, or important information about the product or its further uses. It does not indicate a dangerous or damaging situation. TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 9: Name Plate

    The storage temperature should be between -40 ... 85 °C (-40 ... 185 °F). The storage time is basically indefinite. However, the warranty conditions stipulated in the order confirmation of the supplier are valid. 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 10: Installation Safety Information

    Incorrect parameter values can cause the valve to move unexpectedly. This can lead to process failures and result in injuries. Before recommissioning a TZIDC, TZIDC-110, TZIDC-120 positioner that was used at another location, the device must always be reset to factory settings. Never start Autoadjust before restoring factory settings.
  • Page 11: Returning Devices

    According to EC guidelines for hazardous materials, the owner of hazardous waste is responsible for its disposal or must observe the following regulations for shipping purposes: All devices delivered to ABB Automation Products GmbH must be free from any hazardous materials (acids, alkalis, solvents, etc.).
  • Page 12: Disposal

    If it is not possible to dispose of old equipment properly, ABB Service can accept and dispose of returns for a fee. 1.13.2 RoHS Directive 2002/95/EC With the Electrical and Electronic Equipment Act (ElektroG) in Germany, the European Directives 2002/96/EC (WEEE) and 2002/95/EC (RoHS) are translated into national law.
  • Page 13: Ex Relevant Safety Instructions

    IMPORTANT (NOTE) – Use in areas with combustible dust • To prevent loss of its ignition-proof classification, the housing may not be opened. • Use only cable glands that conform to protection type ≥ IP 65. • Avoid hazardous sliding brush discharges. 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 14: Design And Function

    In both cases, the “mechanical position indicator” (8) must be installed. 1) TZIDC only Functionality The TZIDC, TZIDC-110, TZIDC-120 is an electronically configurable positioner with communication capabilities designed for mounting on pneumatic linear or rotary actuators. Fully automatic determination of the control parameters and adaptation to the final control element yield considerable time savings and an optimal control behavior.
  • Page 15: Mounting

    Incorrect parameter values can cause the valve to move unexpectedly. This can lead to process failures and result in injuries. Before recommissioning a TZIDC, TZIDC-110, TZIDC-120 positioner that was used at another location, the device must always be reset to factory settings. Never start Autoadjust before restoring factory settings.
  • Page 16 During installation make sure that the actuator travel or rotation angle for position feedback is implemented correctly. The maximum rotation angle for position feedback is 60° when installed on linear actuators and 120° on rotary actuators. The minimum angle is always 25°. TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 17: Mounting On Linear Actuators

    Screw (1) and shim (2) for mounting to cast iron yoke • Two U-bolts (7) with two shims (8) and two nuts (9) for mounting to columnar yoke Required tools: Wrench, size 10 / 13 Allen key, size 4 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 18 Attach the mount bracket (1) with screws (2) and shims (3) to the proper holes on the positioner housing. Tighten the screws as evenly as possible to ensure subsequent linearity. Align the mount bracket in the oblong hole to ensure that the operating range is symmetrical (lever moves between the arrows (4)) TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 19 Add the washers (4) and nuts (5). Hand tighten the nuts IMPORTANT (NOTE) Adjust the height of the positioner on the cast iron yoke or columnar yoke until the lever is horizontal (based on visual check) at half stroke of the valve. 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 20 Adjust the actuator stroke to make use of as large an angle of rotation as possible (symmetrical around the center position). Recommended range for linear actuators: between -28 ... 28° Minimum angle: 25° IMPORTANT (NOTE) After mounting the unit check whether the positioner is operating within the sensor range. TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 21: Mounting On Rotary Actuators

    M6 (4), spring washers (3) and shim (2) to attach the mounting bracket (6) on the positioner • each four screws M5 (7), spring washers (8) and shim (9) to attach the mounting bracket on the actuator Required tools: Wrench, size 10 / 13 Allen key, size 3 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 22 • Place the adapter in the proper position on the feedback shaft and fasten with set screws (3). One of the set screws must be locked in place on the flat side of the feedback shaft TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 23 2. Attach mounting bracket on the positioner Fig. 13 1 Mounting bracket 3. Attach positioner to the actuator Fig. 14 IMPORTANT (NOTE) After mounting the unit check whether the operating range for the actuator matches the sensor range on the positioner. 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 24: Electrical Connections

    Electrical connections Electrical connections DANGER! Risk of explosion! (TZIDC only) It is prohibited to use the integrated communication interface (LKS) in an Ex area. Never use the integrated communication interface (LKS) on the mainboard with a positioner that is being used in an explosion risk area.
  • Page 25: Screw Terminal Assignments

    3 Module for digital position feedback or terminals of 9 Grounding screw the shutdown module 4 Installation kit for digital position feedback, either proximity switches or 24 V microswitches 5 Same as 4 1) TZIDC only 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 26: Jumper Configuration On Mainboard (Tzidc-120 Only)

    Electrical connections Jumper configuration on mainboard (TZIDC-120 only) M00494 Fig. 17 1 Simulation 2 Write access There are two jumpers on the mainboard that can be used to activate or block simulation mode and write access. Set the jumpers as shown below: M00495 Fig.
  • Page 27: Cable Entry

    2. Rotate the position indicator on the shaft to the desired position. 3. Attach the housing cover. 4. Affix the symbol label to mark the minimum and maximum valve positions on the housing cover. IMPORTANT (NOTE) The adhesive labels are located on the inside of the cover. 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 28: Mechanical Digital Feedback With Proximity Switches

    2. Set min. contact (2, upper washer); fasten the lower washer with the special adjustment retainers and rotate upper disk manually to adjust. 3. Connect the micro switch. 4. Attach the housing cover and screw onto housing; hand-tighten screws. TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 29: Pneumatic Connection

    Pneumatic connection Pneumatic connection IMPORTANT (NOTE) The TZIDC, TZIDC-110, TZIDC-120 positioner must be supplied with instrument air that is free of oil, water and dust. The purity and oil content should meet the requirements of Class 3 according to DIN/ISO 8573-1.
  • Page 30 Arrange the connections according to their marks: Designation Pipe connection Air supply, pressure 1.4 ... 6 bar (20 ... 90 psi) OUT1 Output pressure for actuator OUT2 Output pressure for actuator (2nd connection with double-acting actuator) TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 31: Commissioning

    Autoadjust then runs again. IMPORTANT (NOTE) Autoadjust does not always result in optimum control conditions. 1) The zero position is determined automatically and saved during Autoadjust (counter-clockwise (CTCLOCKW) for linear actuators and clockwise (CLOCKW) for part-turn actuators). 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 32: Operating Modes

    1) Since self-optimization in operating mode 1.0 is subject to several factors during control operation with adaptation, incorrect adjustments could be made over an extended period. 2) Position not active 3) For high-speed mode: Press simultaneously TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 33: Sample Parameters

    • Press twice briefly is displayed • Release is displayed 3. Select parameter 3.2: • Press and hold • Press twice briefly is displayed • Release 4. Change parameter settings: • Press briefly to select 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 34 3 to 0 The new parameter setting is saved and the positioner automatically returns to the working level and continues to run in the operating level that was active before calling up the configuration level. TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 35: Tzidc-110 / Tzidc-120

    Commissioning TZIDC-110 / TZIDC-120 bieten 1. Feed in pneumatic supply power 2. Connect the bus to the bus terminals with any polarity (or supply power 9 ... 32 V DC) ° is displayed 3. Check mount: • Press and hold down ;...
  • Page 36: Operating Modes

    ° ° Manual adjustment in the operating range Adjust with conf conf ° ° Manual adjustment in the sensor range Adjust with conf conf 1) Positioning not active. 2) for high-speed mode: Press simultaneously. TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 37: Sample Parameters

    Press and release twice, is displayed • Release is displayed 3. Select parameter 3.2: • Press and hold down • Press and release twice, is displayed • Release 4. Change parameter settings: • Press and release to select 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 38: Maintenance

    Note that the supplied instrument air must be free of oil, water and dust according to DIN/ISO 8573-1 to ensure trouble-free operation. Essentially no maintenance is required for the TZIDC, TZIDC-110, TZIDC-120 positioner. We recommend that you regularly check the built-in filter for pollution.
  • Page 39: Functional Check For Emergency Shutdown Module

    2. Move the slide switch (1) from center position "On" to the upper and lower switch positions ("Off1" or "Off2"), and check whether the actuator is depressurized. 3. Reset the slide switch to the center position ("On") after the functional check. 4. Replace the housing cover. 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 40: Specifications

    5 ... 11 V DC Supply voltage Switching state logical "0" Current > 0.35 mA … < 1.2 mA Switching state logical "1" Current > 2.1 mA normally logical "0" or logical "1" Effective direction (configurable) TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 41: Transmission Data And Influences

    Local connector for LKS (not in Ex area) pneumatics. HART communication via 20 mA signal line with (optional) FSK modem The positioner TZIDC / TZIDC-200 and the emergency shutdown module for meet the requirements regarding: functional safety acc. to IEC 61508 9.1.6...
  • Page 42: Options

    Two switches for digital position feedback (position adjustable within When using proximity switch SJ2_S1N (NO), the TZIDC, the range of 0 ... 100 %, ranges cannot overlap) TZIDC-110, TZIDC-120 positioner may only be used at an Current circuits acc. to DIN 19234 / NAMUR ambient temperature range -25 ...
  • Page 43: Accessories

    FSK modem for HART communication Travel time prolongation PC software for remote configuration and operation Setting range 0 ... 200 seconds, separately for each DSV401 (SMART VISION) with DTM for TZIDC to CD-ROM direction TZIDC-110 9.2.5 Air supply Instrument air free of oil, water and dust to DIN/ISO 9.2.1...
  • Page 44: Transmission Data And Influences

    0 … 100 % Current circuits acc. to DIN 19234 / NAMUR Supply voltage 5 ... 11 V DC Signal current < 1 mA Switching state logical “0“ Signal current > 2 mA Switching state logical “1“ TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 45: Accessories

    Transmission rate IMPORTANT (NOTE) 1 AO Function block Block types When using SJ2_S1N (NO), the TZIDC positioner may only 1 PID block be used at an ambient temperature range from -25 ... 85 °C (-13 ... 185 °F). 1 Resource block...
  • Page 46: Device Name

    10 K below operating temperature) Supply pressure 1.4 ... 6 bar (20 ... 90 psi) IMPORTANT (NOTE) Do not exceed the maximum operating pressure of the actuator! Air consumption < 0.03 kg/h / 0.015 scfm (independent of supply pressure) TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 47: Housing

    (20.31 ... 90 psi) the supervisory process control system at any time. Mechanical position indicator Indicator disk Cover with transparent dome Symbol label Extension shaft 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 48: Ex Relevant Specifications

    1) When using the plug-in module for "Digital Feedback" in Temperature Class T6, the maximum permissible ambient temperature range is -40 … 35 °C. Housing surface temperature Ambient temperature range (II 2 D) T81 °C -40 ... 70 °C T61 °C -40 ... 50 °C T51 °C -40 ... 40 °C TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 49 The local communication interface (LKS) may only be operated at Um ≤ 30 V DC outside the potentially explosive area. • The equipment may only be used as a II 2 D type device in areas where the level of mechanical danger is "low". 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 50: Iecex Issue No. 3

    -40 ... 40 °C -40 ... 50 °C Electrical data for type TZIDC with marking Ex ia IIC resp. Ex ib IIC In type of protection "Intrinsic Safety" (Ex ia IIC resp. Ex ib IIC) only for the connection to a certified intrinsically safe circuit with...
  • Page 51 (Terminals +81 / -82) Switch output U = 11 VDC (Terminals +83 / -84) Optionally the following modules are allowed to be used with type TZIDC Plug-In module for digital feedback U = 5 ... 11 VDC (Terminals +51 / -52 resp.
  • Page 52: Csa International

    Class I, Div 1, Groups A, B, C and D; Class II, Div 1, Groups E, F and G Class III, Enclosure Type 4X: Model TZIDC, P/N V18345-x0x2x2xx0x Intelligent Positioner intrinsically safe with entity parameters of: Terminals 11 / 12...
  • Page 53 The "x" in P/N denotes minor mechanical variations or optional features. • Do not use the local communication interface (LKS) in hazardous areas. • Each pair of conductors for each intrinsic safety circuit must be shielded. 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 54: Csa Certification Record

    Class I, Div 1, Groups A, B, C and D; Class II, Div 1, Groups E, F, and G, Class III, Div 1, Enclosure Type 4X: Model TZIDC, P/N V18345-x0x2x2xx0x Intelligent Positioner Input rated 30 V DC; max.4 … 20 mA Output pressure Max.
  • Page 55: Fm Approvals

    Ex relevant specifications 10.1.5 FM Approvals TZIDC Positioner, Model V18345-a0b2c2de0f IS/I,II,III/1/ABCDEFG/T4 Ta = 85 °C – 901064/7/4; Enity; NI/I/2/ABCD/T4 Ta = 85 °C; S/II,III/2/FG/T4 Ta =85 °C; Type 4XMax Enity Parameters: Per Control Drawings a = Case/mounting – 1, 2, 3, 4 or 9 b = Input/communication port –...
  • Page 56: Fm Control Document

    Ex relevant specifications 10.1.6 FM Control Document TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 57 Ex relevant specifications 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 58 Ex relevant specifications TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 59 Ex relevant specifications 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 60: Tzidc-110

    Only for connection to a programmer or PC outside the interface (LKS) and program potentially explosive area. interface (X5) IMPORTANT (NOTE) • The local communication interface (LKS) and program interface (X5) may only be operated outside the potentially explosive area. TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 61: Iecex Issue No. 3

    -40 ... 65 °C -40 ... 40 °C -40 ... 50 °C Electrical data for type TZIDC-110 with marking Ex ia IIC T6 resp. Ex ib IIC T6 Input circuit In type of protection "Intrinsic Safety" (Ex ia IIC resp. Ex ib IIC) (terminals +11, -12 resp.+, -)
  • Page 62 The intrinsically safe circuits themselves are safe galvanically separated up to a voltage of 60 V. The "Local interface for communication (LKS) and programming interface (X5)" is connected with the signal circuit. Electrical data for type TZIDC-110 with marking Ex nA IIC T6 Input circuit U = 9 ... 32 VDC; 10.5 mA...
  • Page 63: Csa International

    Class I, Div 2, Groups A, B, C and D; Class II, Div 2, Groups E, F, and G, Class III, Enclosure Type 4X: Model TZIDC-110, P/N V18346-x032x2xx0x Intelligent Positioner Input rated 32 V DC; max.15 mA (powered by a SELV...
  • Page 64: Csa Certification Record

    Class I, Div 1, Groups A, B, C and D; Class II, Div 1, Groups E, F, and G, Class III, Div 1, Enclosure Type 4X: Model TZIDC-110, P/N V18346-x032x2xx0x Intelligent Positioner Input rated 32 V DC; max. 15 mA (powered by a SELV...
  • Page 65: Fm Approvals

    Ex relevant specifications 10.2.5 FM Approvals TZIDC-110 Positioner, Model V18346-a032b2cd0e IS/I,II,III/1/ABCDEFG/T6,T5,T4 Ta = 40 °C, 55 °C, 85 °C-901265 Entity, FISCO Entity and FISCO Parameters Terminals Type Groups Parameters Vmax Imax +11 / -12 Entity 24 V 250 mA 1.2 W 2.8 nF...
  • Page 66: Fm Control Document

    Ex relevant specifications 10.2.6 FM Control Document TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 67 Ex relevant specifications 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 68 Ex relevant specifications TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 69: Tzidc-120

    Only for connection to a programmer or PC outside the interface (LKS) and program potentially explosive area. interface (X5) IMPORTANT (NOTE) • The local communication interface (LKS) and program interface (X5) may only be operated outside the potentially explosive area. 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 70: Iecex Issue No. 3

    -40 … 65 °C -40 … 40 °C -40 … 50 °C Electrical data for type TZIDC-120 with marking Ex ia IIC T6 resp. Ex ib IIC T6 Input circuit In type of protection "Intrinsic Safety" (Ex ia IIC resp. Ex ib IIC) (terminals +11 / -12 resp.
  • Page 71 The intrinsically safe circuits themselves are safe galvanically separated up to a voltage of 60 V. The "Local interface for communication (LKS) and programming interface (X5)" is connected with the signal circuit. Electrical data for type TZIDC-120 with marking Ex nA IIC T6 Input circuit U = 9 … 32 VDC; 11.5 mA...
  • Page 72: Csa International

    Class I, Div 2, Groups A, B, C and D; Class II, Div 2, Groups E, F, and G, Class III, Enclosure Type 4X: Model TZIDC-120, P/N V18347-x042x2xx0x Intelligent Positioner Input rated 32 V DC; max.15 mA (powered by a SELV...
  • Page 73: Csa Certification Record

    Class I, Div 1, Groups A, B, C and D; Class II, Div 1, Groups E, F, and G, Class III, Div 1, Enclosure Type 4X: Model TZIDC-120, P/N V18347-x042x2xx0x Intelligent Positioner Input rated 32 V DC; max. 15 mA (powered by a SELV...
  • Page 74: Fm Approvals

    Ex relevant specifications 10.3.5 FM Approvals TZIDC-120 Positioner, Model V18347-a042b2cd0e IS/I,II,III/1/ABCDEFG/T6,T5,T4 Ta = 40 °C, 55 °C, 85 °C-901265 Entity, FISCO Entity and FISCO Parameters Terminals Type Groups Parameters Vmax Imax +11 / -12 Entity 24 V 250 mA 1.2 W 2.8 nF...
  • Page 75: Fm Control Document

    Ex relevant specifications 10.3.6 FM Control Document 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 76 Ex relevant specifications TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 77 Ex relevant specifications 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 78: Parameter Descriptions

    Parameter descriptions 11 Parameter descriptions 11.1 TZIDC 11.1.1 Parameter overview M00487 Abb. 22: Parameter overview TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 79: Parameter Description

    Spring action (Y2) Federwirkung (Y2) P6.4 DANG_DN 0.0 … 45.0 Dead angle close Toter Winkel 0% P6.5 DANG_UP Dead angle open Toter Winkel 100% 55.0 … 100.0 100.0 P6.6 EXIT Function NV_SAVE Return Zurück z. Arbeitsebene 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 80 P11._ FS/IP P11.0 FAIL_POS ACTIVE, INACTIVE INACTIVE Save position Sicherheitsstellung P11.1 FACT_SET Function START Factory setting Werkseinstellung P11.2 IP-TYP NO_F_POS,F_SAFE_1,F_SAFE_2, [CUSTOM] I/P module type Typ des l/P-Moduls F_FREEZE1,F_FREEZE2 P11.3 EXIT Function NV_SAVE Return Zurück z. Arbeitsebene TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 81: Tzidc-110 / Tzidc-120

    Parameter descriptions 11.2 TZIDC-110 / TZIDC-120 11.2.1 Parameter overview M00502 Fig. 23: Parameter overview 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 82: Parameter Description

    P11._ FS/IP P11.0 FAIL_POS ACTIVE, INACTIV INACTIV Save position selection P11.1 FACT_SET Function Factory setting P11.2 IP_TYP NO_F_POS,F_SAFE_1, F_SAF NO_F_POS I/P module type E_2, F_FREEZE1, F_FREEZE2 P11.3 EXIT Function Return to operat. level 1) only TZIDC-110 TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 83: Appendix

    Identification for intended use in potentially explosive atmospheres according Protection ATEX directive (marking in addition to CE marking) IEC standards FM Approvals (US) CSA International (Canada) IMPORTANT (NOTE) All documentation, declarations of conformity, and certificates are available in ABB's download area. www.abb.com/instrumentation 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 84 Appendix TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN...
  • Page 85 Which substances have come into contact with the device? We hereby state that the devices / components shipped have been cleaned and are free from any dangerous or poisonous substances. Town/city, date Signature and company stamp 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 86: Index

    Setpoint current............31 Integrated management system ......11 Setting the mechanical feedback......27 Intended use ..............6 Specifications............40 Storage conditions .............9 Jumper configuration on mainboard (TZIDC-120 only)..............26 Target groups and qualifications........7 Maintenance ............38 Tolerance band ............36 Mechanical digital feedback with proximity switches Transmission data and influences ....41, 45, 48 ................28...
  • Page 87 Index Travel ............40, 44, 47 TZIDC ........... 31, 40, 50, 81 Warranty ..............7 TZIDC-110 ............43, 63 Warranty provisions ...........7 TZIDC-110 / TZIDC-120 ........35, 84 TZIDC-120 ............47, 72 Zero position ............33, 37 Change from one to two columns 42/18-84-EN TZIDC, TZIDC-110, TZIDC-120...
  • Page 88 ABB has Sales & Customer Support expertise in over The Company’s policy is one of continuous product 100 countries worldwide. improvement and the right is reserved to modify the information contained herein without notice. www.abb.com/instrumentation Printed in the Fed. Rep. of Germany (09.2011) ©...

This manual is also suitable for:

Tzidc-120Tzidc-110