Table of Contents

Advertisement

TZIDC DIGITAL POSITIONER | CI/TZIDC/ATEX/IECEX-EN REV. C

IECEx Ex i

Ex marking
Marking
Type Examination Test Certificate
Type
Standards
Temperature Data
Temperature class
T4
T6*
*
When using the 'Limit monitor' plug−in module in temperature class T6, the
maximum permissible ambient temperature range is −40 to 35 °C.
Electrical Data
In 'intrinsically safe Ex ib IIC / Ex ia IIC' type of protection, only
for connection to a certified intrinsically safe circuit.
Current circuit (terminal)
Signal circuit
(+11 / −12)
Contact input
(+81 / −82)
Switch output
(+83 / −84)
Local communication
Only for connection to a programming device using
interface (LCI)
an ABB LCI adapter (Um ≤ 30 V DC) outside the
Change from two to one column
Ex ia IIC T6 or T4 Gb
Ex ib IIC T6 or T4 Gb
IECEx TUN 04.0015X
Intrinsic safety 'i'
IEC 60079-0:2011
IEC 60079-11:2011
Ambient temperature Ta
TZIDC Ex ia IIC
TZIDC Ex ib IIC
−40 to 85 °C
−40 to 85 °C
−40 to 40 °C*
−40 to 40 °C
Electrical information (maximum values)
U
= 30 V
C
i
i
I
= 320 mA
L
= negligibly small
i
i
P
= 1.1 W
i
U
= 30 V
C
= 14.5 nF
i
i
I
= 320 mA
L
= negligibly small
i
i
P
= 1.1 W
i
U
= 30 V
C
= 14.5 nF
i
i
I
= 320 mA
L
= negligibly small
i
i
P
= 500 mW
i
hazardous area.
The following modules may be operated as an option:
Current circuit (terminal)
Plug-in module for limit
monitor
(+51 / −52)
(+41 / −42)
Plug-in module for
analog position
feedback
(+31 / −32)
Special conditions
For the 'Limit monitor with proximity switches' circuit,
measures outside of the device must be implemented to
prevent the rated voltage from being up-scaled by more than
40 % due to transient disturbances.
It is only permissible to connect, disconnect, and switch live
circuits during installation or maintenance, or for the
purpose of carrying out repairs. Note: It is considered very
unlikely that a hazardous atmosphere would be present in
Zone 2 at the same time that installation, maintenance or
repair work was being carried out.
Only non-flammable gases may be used for pneumatic power
supply.
= 6.6 nF
Only use suited cable entries that meet the requirements of
EN 60079-15.
Electrical information (maximum values)
U
= 30 V
Ci = 3.7 nF
i
I
= 320 mA
Li = negligibly small
i
P
= 250 mW
i
U
= 30 V
Ci = 6.6 nF
i
I
= 320 mA
Li = negligibly small
i
P
= 1.1 W
i
9

Advertisement

Table of Contents
loading