TZID-C
Operating Instructions
Intelligent Positioner
42/18-64 EN
TZID-C
Rev. 4.0
%

Advertisement

Table of Contents
loading

Summary of Contents for ABB TZID-C

  • Page 1 TZID-C Intelligent Positioner Operating Instructions 42/18-64 EN Rev. 4.0 TZID-C...
  • Page 2 Mounting to linear actuators...
  • Page 3 Mounting to rotary actuators M6 screws M5 screws...
  • Page 4: Mechanical Mounting

    Brief operating instructions Brief operating instructions Read and observe the safety instructions in chapter 1 of these operating instructions. Caution Mechanical mounting see fold-out drawing Pneumatic connection • Connect the air supply to the in port. Air supply range must be between 1.4 and 6 bar (20 to 90 psi).
  • Page 5 Brief operating instructions Commissioning 1. Turn on the air supply to the positioner. 2. Apply the 4...20 mA analog input signal to the positioner. 3. Check for proper mounting: Press and hold MODE Additionally briefly press until mode 1.3 (manual adjustment within the sensor range) is displayed.
  • Page 6: Selecting Operating Mode

    Brief operating instructions 7. Adjust the tolerance band (only necessary for critical actuators, e.g. especially small ones). See “P1.2 Tolerance band” on page 55. Usually, this step is not required. 8. If required test the settings. See “P1.3 Test” on page 56 for details. 9.
  • Page 7 Brief operating instructions Mode 1.2: Manual adjustment within the stroke range • Press and hold MODE • Additionally briefly press as often as required. ° • is displayed. conf • Release MODE ° • is displayed. conf • Press to adjust the position within the stroke range. Mode 1.3: Manual adjustment within the sensor range •...
  • Page 8: Parameter Setting Example

    Brief operating instructions Parameter setting example: "Changing valve action from direct to reverse" Starting situation: the TZID-C is operating on the operating level in an arbitrary mode. 1. Change over to the configuration level: Simultaneously press and hold In addition, briefly press ENTER Wait until countdown from 3 to 0 has run down.
  • Page 9 Brief operating instructions 5. Change over to parameter 2.7 "EXIT" and save the new setting: Press and hold MODE In addition, 4 x briefly press ° is displayed. conf Release MODE Briefly press to select "NV_SAVE. Press and hold until the displayed countdown from 3 to 0 has run down. ENTER The positioner saves the new setting and automatically returns to the operating level.
  • Page 10 Table of contents Table of Contents 0 Brief operating instructions ..................a 1 Safety and precautions ....................1 General ........................1 Explanation of warning signs and notes..............2 Notes on electrical and pneumatic safety .............2 Proper use .........................2 Qualified personnel ....................2 2 Manufacturer’s information ..................