Ex relevant specifications
7.3.7

CSA Certification Record

Certificate:
Class 2258 04
Class I, Div 1, Groups A, B, C and D;
Class II, Div 1, Groups E, F, and G,
Class III, Div 1, Enclosure Type 4X:
Model TZIDC-120, P/N V18347-x042x2xx0x Intelligent Positioner
Input rated
Intrinsically safe with entity parameters of:
Terminals 11 / 12
Terminals 85 / 86
Terminals 41 / 42
When installed per installation Drawing No 901265
Temperature Code
Max. Ambient
IMPORTANT (NOTE)
The "x" in P/N denotes minor mechanical variations or optional features.
Do not use the local communication interface (LKS) in hazardous areas.
Each pair of conductors for each intrinsic safety circuit must be shielded.
64
V max = 24 V
I max = 250 mA
C
= 2.8 nF
i
L
= 7.2 uH
i
U max = 30 V
I max = 50 mA
C
= 3.8 nF
i
L
= 0 uH
i
U max = 16 V
I max = 20 mA
C
= 60 nF
i
L
= 100 uH
i
TZIDC, TZIDC-110, TZIDC-120
1649904 (LR 20312)
PROCESS CONTROL EQUIPMENT –
Intrinsically Safe, Entity – For Hazardous
Locations
32 V DC; max. 15 mA (powered by a SELV
Circuit)
T4
85 Deg C
CI/TZIDC/110/120-EN