Commissioning

6.1

TZIDC

bieten
1. Feed in pneumatic supply power
2. Feed in electrical supply power
3. Check mount:
4. Run Autoadjust
IMPORTANT (NOTE)
Autoadjust is available for software version 2.XX and higher.
For linear actuators
For part-turn actuators
If Autoadjust is successful, the parameters will be stored automatically and the positioner will
revert to operating mode 1.1.
If an error occurs during Autoadjust, the process will be terminated with an error message. If
this happens, press and hold down
to the operating level, mode 1.3 (manual adjustment within the sensor range). The mount is
checked and corrected if necessary. Autoadjust then runs again.
IMPORTANT (NOTE)
Autoadjust does not always result in optimum control conditions.
1) The zero position is determined automatically and saved during Autoadjust (counter-clockwise (CTCLOCKW) for
linear actuators and clockwise (CLOCKW) for part-turn actuators).
CI/TZIDC/110/120-EN
Feed in setpoint current 4 ... 20 mA (terminals +11 / -12)
Press and hold
, plus
the sensor range) is displayed. Release
Press
or
to move the actuator into the mechanical end position; check the end
positions; rotation angle is displayed in degrees; for high-speed mode, press
simultaneously
Recommended range:
-
between -28 ... 28° for linear actuators
-
between -57 ... 57° for part-turn actuators
Minimum angle: 25°
1)
:
Press and hold down
Press
again and hold down until the countdown ends
Release
; this starts Autoadjust
1)
:
Press
and hold down until
Press
again and hold down until the countdown ends
Release
; this starts Autoadjust
TZIDC, TZIDC-110, TZIDC-120
or
until operating mode 1.3 (manual adjustment within
until
is displayed; release the control button
is displayed; release the control button
or
for approximately three seconds. The unit will switch
Commissioning
and
31