Neutral Current - GE N60 Instruction Manual

Network stability and synchrophasor
Hide thumbs Also See for N60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
The phase directional element responds to the forward load current. In the case of a following reverse fault, the
element needs some time—in the order of 8 ms—to establish a blocking signal. Some protection elements, such as
instantaneous overcurrent, respond to reverse faults before the blocking signal is established. Therefore, a
coordination time of at least 10 ms must be added to all the instantaneous protection elements under the
supervision of the phase directional element. If current reversal is of concern, a longer delay—in the order of 20
ms—is needed.

5.7.5 Neutral current

5.7.5.1 Menu
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  NEUTRAL CURRENT
 NEUTRAL CURRENT
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
Figure 5-122: Phase directional logic
 NEUTRAL TOC 1
 NEUTRAL TOC 6
 NEUTRAL IOC 1
 NEUTRAL IOC 12
GROUPED ELEMENTS
See below
See page 5-235
5
5-233

Advertisement

Table of Contents
loading

Table of Contents