GE N60 Instruction Manual page 32

Network stability and synchrophasor
Hide thumbs Also See for N60:
Table of Contents

Advertisement

SPECIFICATIONS
Dropout level:
Level accuracy:
Time delay:
Timer accuracy:
Operate time:
Typical times are average operate times including variables such as frequency change instance, test method, and so on, and can vary by
2
±0.5 cycles.
RATE OF CHANGE OF FREQUENCY
df/dt trend:
df/dt pickup level:
df/dt dropout level:
df/dt level accuracy:
Overvoltage supv.:
Overcurrent supv.:
Pickup delay:
Reset delay:
Timer accuracy:
95% settling time for df/dt:
Operate time:
Typical times are average operate times including variables such as frequency change instance, test method, and so on, and can vary by
±0.5 cycles.
SYNCHROCHECK
Max voltage difference:
Max angle difference:
Max freq. difference:
Hysteresis for max. freq. diff.:
Dead source function:
S-CLS MAX dF:
S-CLS MIN dF:
V2 MAG CORR FACTOR:
V2 ANGLE SHIFT:
POWER SWING DETECT
Functions:
Characteristic:
Measured impedance:
Blocking / tripping modes:
Tripping mode:
Current supervision:
Pickup level:
Dropout level:
Fwd / reverse reach (sec. Ω):
Left and right blinders (sec. Ω):
Impedance accuracy:
Fwd / reverse angle impedances:
Angle accuracy:
Characteristic limit angles:
Timers:
Timer accuracy:
2-18
pickup – 0.03 Hz
±0.001 Hz
0 to 65.535 s in steps of 0.001
±3% of operate time or ±1/4 cycle (whichever is greater)
typically 4 cycles at 0.1 Hz/s change
typically 3.5 cycles at 0.3 Hz/s change
typically 3 cycles at 0.5 Hz/s change
increasing, decreasing, bi-directional
0.10 to 15.00 Hz/s in steps of 0.01
96% of pickup
80 mHz/s or 3.5%, whichever is greater
0.100 to 3.000 pu in steps of 0.001
0.020 to 30.000 pu in steps of 0.001
0 to 65.535 s in steps of 0.001
0 to 65.535 s in steps of 0.001
±3% of operate time or ±1/4 cycle (whichever is greater)
<24 cycles
typically 9.5 cycles at 2 × pickup
typically 8.5 cycles at 3 × pickup
typically 6.5 cycles at 5 × pickup
0 to 400000 V in steps of 1
°
0 to 100
in steps of 1
0.00 to 2.00 Hz in steps of 0.01
0.00 to 0.10 Hz in steps of 0.01
None, LV1 & DV2, DV1 & LV2, DV1 or DV2, DV1 xor DV2, DV1 & DV2 (L = Live, D = Dead)
0.10 to 2.00 Hz in steps of 0.01
0.00 to 1.00 Hz in steps of 0.01
0.10 to 10.00 in steps of 0.01
°
°
°
-180
to +180
in steps of 1
Power swing block, out-of-step trip
Mho or Quad
Positive-sequence
2-step or 3-step
Early or Delayed
0.050 to 30.000 pu in steps of 0.001
97 to 98% of pickup
0.10 to 500.00 Ω in steps of 0.01
0.10 to 500.00 Ω in steps of 0.01
±5%
40 to 90° in steps of 1
±2°
40 to 140° in steps of 1
0.000 to 65.535 s in steps of 0.001
±3% of operate time or ±1/4 cycle (whichever is greater)
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL