GE N60 Instruction Manual page 488

Network stability and synchrophasor
Hide thumbs Also See for N60:
Table of Contents

Advertisement

CONTROL ELEMENTS
CHAPTER 5: SETTINGS
— These settings specify FlexLogic operands that constitute the first (A) input of the
8BIT SW 1 ARG A0 to 8BIT SW 1 ARG A7
switch. These operands are routed to the output operands if the control input is in the "Off" position.
— These settings specify FlexLogic operands that constitute the second (B) input of the
BIT SW 1 ARG B0 to 8BIT SW 1 ARG B7
switch. These operands are routed to the output operands if the control input is in the "On" position.
— This setting specifies FlexLogic operands to control the routing between the A and B inputs of the
8BIT SW 1 CONTROL
switch. If the control operand is in the "Off" state, the first (A) input is switched to the output. If the control operand is in the
"On" state, the second (B) input is switched to the output. The switching takes place instantaneously.
Figure 5-160: 8-bit switch logic
5
5-294
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL

Advertisement

Table of Contents
loading