Settings - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
3.4
Table 1:
AISVBAS Non group settings (basic)
Name
Values (Range)
PhaseAngleRef
TRM - Channel 1
TRM - Channel 2
TRM - Channel 3
TRM - Channel 4
TRM - Channel 5
TRM - Channel 6
TRM - Channel 7
TRM - Channel 8
TRM - Channel 9
TRM - Channel 10
AIM - Channel 1
AIM - Channel 2
AIM - Channel 3
AIM - Channel 4
AIM - Channel 5
AIM - Channel 6
AIM - Channel 7
AIM - Channel 8
AIM - Channel 9
AIM - Channel 10
Table 2:
TRM_6I_4U Non group settings (basic)
Name
Values (Range)
CTStarPoint1
FromObject
ToObject
CTsec1
0.1 - 10.0
CTprim1
1 - 99999
CTStarPoint2
FromObject
ToObject
CTsec2
0.1 - 10.0
Table continues on next page
Technical manual
have corresponding primary quantity, the 1:1 ratio shall be set for the used analogue
inputs on the IED, For example, HZPDIF.
Parameter IBase used by the tested function is set equal to the rated CT primary
current.
Parameter UBase used by the tested function is set equal to the rated primary phase-
to-phase voltage.
Parameter SBase used by the tested function is set equal to sqrt(3)* IBase* UBase for
three-phase power system.

Settings

Dependent on ordered IED type.
Unit
Step
-
-
Unit
Step
-
-
A
0.1
A
1
-
-
A
0.1
Default
Description
TRM - Channel 1
Reference channel for phase angle
presentation
Default
Description
ToObject
ToObject= towards protected object,
FromObject= the opposite
1
Rated CT secondary current
1000
Rated CT primary current
ToObject
ToObject= towards protected object,
FromObject= the opposite
1.0
Rated CT secondary current
Section 3
Analog inputs
49