Settings - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
13.5.5
13.5.6
13.5.7
Technical manual
Table 331:
B16I Output signals
Name
Type
OUT
INTEGER

Settings

The function does not have any parameters available in local HMI or Protection and
Control IED Manager (PCM600)
Monitored data
Table 332:
B16I Monitored data
Name
Type
OUT
INTEGER
Operation principle
The Boolean 16 to integer conversion function (B16I) will transfer a combination of up to
16 binary inputs INx, where 1≤x≤16, to an integer. Each INx represents a value according
to the table below from 0 to 32768. This follows the general formula: INx = 2
1≤x≤16. The sum of all the values on the activated INx will be available on the output
OUT as a sum of the integer values of all the inputs INx that are activated. OUT is an
integer. When all INx (where 1≤x≤16) are activated, that is = Boolean 1, it corresponds to
that integer 65535 is available on the output OUT. The B16I function is designed for
receiving up to 16 booleans input locally. If the BLOCK input is activated, it will freeze
the output at the last value.
Values of each of the different OUTx from function block B16I for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output OUT
on the function block B16I
Name of input
Type
IN1
BOOLEAN
IN2
BOOLEAN
IN3
BOOLEAN
IN4
BOOLEAN
IN5
BOOLEAN
IN6
BOOLEAN
Table continues on next page
Description
Output value
Values (Range)
Unit
-
-
Default
Description
0
Input 1
0
Input 2
0
Input 3
0
Input 4
0
Input 5
0
Input 6
Section 13
Logic
Description
Output value
x-1
where
Value when
Value when
activated
deactivated
1
0
2
0
4
0
8
0
16
0
32
0
491