Operation principle

The Loss of excitation (LEXPDIS ,40) protection in the IED measures the apparent
positive sequence impedance seen out from the generator.
Measured mode
Measured apparent impedance
V
Z
posseq
posseq
=
I
posseq
EQUATION2051-ANSI V1 EN
There are three characteristics in LEXPDIS (40) protection as shown in figure 71.
Naimly:
Offset mho circle for Z1
Offset mho circle for Z2
Directional blinder
X
IEC06000455 V2 EN
Figure 71:
Three characteristics in LEXPDIS (40) protection
When the apparent impedance reaches the zone Z1 this zone will operate, normally with
a short delay. The zone is related to the dynamic stability of the generator.
(Equation 39)
Underexitation protection
Underexcitation Protection
Restrain area
Restrain area
R
R
Directional
blinder
Z1, Fast zone
Z2, Slow zone
IEC06000455-2-en.vsd
1MRK 502 048-UUS A
Technical manual