Technical data

Table 385:
L4UFCNTtechnical data
Function
Counter value
Max. count up speed
Disturbance report
Functionality
Complete and reliable information about disturbances in the primary and/or in the
secondary system together with continuous event-logging is accomplished by the
disturbance report functionality.
Disturbance report DRPRDRE, always included in the IED, acquires sampled data of all
selected analog input and binary signals connected to the function block with a, maximum
of 40 analog and 96 binary signals.
The Disturbance report functionality is a common name for several functions:
Sequential of events
Indications
Event recorder
Trip value recorder
Disturbance recorder
The Disturbance report function is characterized by great flexibility regarding
configuration, initiating conditions, recording times, and large storage capacity.
A disturbance is defined as an activation of an input to the AnRADR or BnRBDR function
blocks, which are set to trigger the disturbance recorder. All connected signals from start
of pre-fault time to the end of post-fault time will be included in the recording.
Every disturbance report recording is saved in the IED in the standard Comtrade format
as a reader file HDR, a configuration file CFG, and a data file DAT. The same applies to
all events, which are continuously saved in a FIFO-buffer. The local HMI is used to get
information about the recordings. The disturbance report files may be uploaded to
PCM600 for further analysis using the disturbance handling tool.
Range or value
0-65535
5-160 pulses/s
Section 14
Monitoring
Accuracy
-
-