Operation Principle - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 7
Impedance protection
Name
Values (Range)
Z2Rev
0.005 - 3000.000
tZ2
0.000 - 60.000
OpModeZ3
Disable-Zone
Enable-Zone
Z3Fwd
0.005 - 3000.000
Z3Rev
0.005 - 3000.000
tZ3
0.000 - 60.000
Table 59:
ZGCPDIS (21G) Group settings (advanced)
Name
Values (Range)
LoadEnchModeZ3
Disabled
Enabled
Table 60:
ZGCPDIS (21G) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
7.2.6
7.2.6.1
7.2.6.2
162
Unit
Step
ohm/p
0.001
s
0.001
-
-
ohm/p
0.001
ohm/p
0.001
s
0.001
Unit
Step
-
-
Unit
Step
-
1

Operation principle

Full scheme measurement
The execution of the different fault loops for phase-to-phase faults are executed in
parallel. The use of full scheme technique gives faster operation time compared to the
switched schemes that uses a pickup element to select correct voltage and current
depending on the fault type.
Impedance characteristic
The distance function consists of three zones. Each zone is self polarized offset mho
characteristics with reverse offset. The operating characteristic is in accordance to figure
67.
Default
Description
30.000
Reverse reach setting for Zone 2
0.500
Time delay to operate for Zone 2
Disable-Zone
Operation mode of Zone 3
30.000
Forward reach setting for Zone 3
30.000
Reverse reach setting for Zone 3
1.000
Time delay to operate for Zone 3
Default
Description
Disabled
Enable load enchroachment mode Zone 3
Default
Description
1
Selection of one of the Global Base Value
groups
1MRK 502 048-UUS A
Technical manual