Monitored Data - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
Table 363:
CMSQI Non group settings (advanced)
Name
Values (Range)
3I0ZeroDb
0 - 100000
3I0HiHiLim
0 - 500000
3I0HiLim
0 - 500000
3I0LowLim
0 - 500000
3I0LowLowLim
0 - 500000
I1ZeroDb
0 - 100000
I1HiHiLim
0 - 500000
I1HiLim
0 - 500000
I1LowLim
0 - 500000
I1LowLowLim
0 - 500000
I1LimHys
0.000 - 100.000
I2ZeroDb
0 - 100000
I2HiHiLim
0 - 500000
I2HiLim
0 - 500000
I2LowLim
0 - 500000
I2LowLowLim
0 - 500000
14.1.5.5
Technical manual
Unit
Step
m%
1
A
1
A
1
A
1
A
1
m%
1
A
1
A
1
A
1
A
1
%
0.001
m%
1
A
1
A
1
A
1
A
1

Monitored data

Table 364:
CMSQI Monitored data
Name
Type
3I0
REAL
3I0ANGL
REAL
I1
REAL
I1ANGL
REAL
I2
REAL
I2ANGL
REAL
Default
Description
500
Zero point clamping
3600
High High limit (physical value)
3300
High limit (physical value)
0
Low limit (physical value)
0
Low Low limit (physical value)
500
Zero point clamping
1200
High High limit (physical value)
1100
High limit (physical value)
0
Low limit (physical value)
0
Low Low limit (physical value)
5.000
Hysteresis value in % of range and is common
for all limits
500
Zero point clamping
1200
High High limit (physical value)
1100
High limit (physical value)
0
Low limit (physical value)
0
Low Low limit (physical value)
Values (Range)
Unit
-
A
-
deg
-
A
-
deg
-
A
-
deg
Section 14
Monitoring
Description
3I0 Amplitude
3I0 Angle
I1 Amplitude
I1 Angle
I2 Amplitude
I2Angle
521

Advertisement

Table of Contents
loading

This manual is also suitable for:

650 seriesReg650 ansi

Table of Contents